{"title":"变压器-1 150kV/20kV布拉加变电站过流和接地故障继电保护设置","authors":"Handoko Rusiana Iskandar, Herry Mulyono, Atik Charisma, Muhammad Reza Hidayat","doi":"10.35313/jitel.v3.i3.2023.181-190","DOIUrl":null,"url":null,"abstract":"The occurrence of a malfunction at the substation results in power outages and losses in the electrical energy distribution system to consumers. Many tests are carried out to see the performance of the protection system, including the parameters of the over current relay (OCR) and ground fault relay (GFR) in the electrical energy distribution system. This research aims to analyze OCR and GFR values, analyze OCR setting, drop-off, and pick-up values, and analyze OCR time characteristics using DigSilent Power Factory 15.1 software based on existing equipment specification data at the Braga substation. The results show an OCR accuracy level of around 94% on the 20 kV and 150 kV sides. Meanwhile, 92.39% on the 20 kV GFR side and 94.87% on the 150 kV side. The setting value for the pick-up current is 0.92 A on the 20 kV side of the GFR and the drop-off current is 0.85 A on the 150 kV side with a pick-up current of 0.39 A and a drop-up current of 0.37 A. Setting a value on the 20kV side is greater than on the 150 kV side due to the difference in current transformer ratio values. The simulation results show that the OCR and GFR characteristic curves on both sides meet the criteria for a protection system with good performance.","PeriodicalId":476867,"journal":{"name":"Jurnal Ilmiah Telekomunikasi, Elektronika, dan Listrik Tenaga","volume":"12 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-09-13","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Overcurrent and ground fault relay protection settings at tranformator-1 150kV/20kV Braga substation\",\"authors\":\"Handoko Rusiana Iskandar, Herry Mulyono, Atik Charisma, Muhammad Reza Hidayat\",\"doi\":\"10.35313/jitel.v3.i3.2023.181-190\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The occurrence of a malfunction at the substation results in power outages and losses in the electrical energy distribution system to consumers. Many tests are carried out to see the performance of the protection system, including the parameters of the over current relay (OCR) and ground fault relay (GFR) in the electrical energy distribution system. This research aims to analyze OCR and GFR values, analyze OCR setting, drop-off, and pick-up values, and analyze OCR time characteristics using DigSilent Power Factory 15.1 software based on existing equipment specification data at the Braga substation. The results show an OCR accuracy level of around 94% on the 20 kV and 150 kV sides. Meanwhile, 92.39% on the 20 kV GFR side and 94.87% on the 150 kV side. The setting value for the pick-up current is 0.92 A on the 20 kV side of the GFR and the drop-off current is 0.85 A on the 150 kV side with a pick-up current of 0.39 A and a drop-up current of 0.37 A. Setting a value on the 20kV side is greater than on the 150 kV side due to the difference in current transformer ratio values. The simulation results show that the OCR and GFR characteristic curves on both sides meet the criteria for a protection system with good performance.\",\"PeriodicalId\":476867,\"journal\":{\"name\":\"Jurnal Ilmiah Telekomunikasi, Elektronika, dan Listrik Tenaga\",\"volume\":\"12 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2023-09-13\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Jurnal Ilmiah Telekomunikasi, Elektronika, dan Listrik Tenaga\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.35313/jitel.v3.i3.2023.181-190\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Jurnal Ilmiah Telekomunikasi, Elektronika, dan Listrik Tenaga","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.35313/jitel.v3.i3.2023.181-190","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
摘要
变电站故障的发生会导致电力中断和电力分配系统对用户的损失。对配电系统中的过流继电器(OCR)和接地故障继电器(GFR)的参数进行了测试,以了解保护系统的性能。本研究旨在基于布拉加变电站现有设备规格数据,利用DigSilent Power Factory 15.1软件对OCR和GFR值进行分析,对OCR整定值、落值和取值进行分析,并对OCR时间特性进行分析。结果表明,在20 kV和150 kV侧,OCR精度水平约为94%。20 kV侧占92.39%,150 kV侧占94.87%。GFR 20kv侧拾取电流设定值为0.92 A, 150kv侧降电流设定值为0.85 A,拾取电流为0.39 A,降电流为0.37 A。20kV侧的设定值大于150kv侧的设定值,这是由于变电流比值的差异。仿真结果表明,两侧的OCR和GFR特性曲线符合保护系统性能良好的标准。
Overcurrent and ground fault relay protection settings at tranformator-1 150kV/20kV Braga substation
The occurrence of a malfunction at the substation results in power outages and losses in the electrical energy distribution system to consumers. Many tests are carried out to see the performance of the protection system, including the parameters of the over current relay (OCR) and ground fault relay (GFR) in the electrical energy distribution system. This research aims to analyze OCR and GFR values, analyze OCR setting, drop-off, and pick-up values, and analyze OCR time characteristics using DigSilent Power Factory 15.1 software based on existing equipment specification data at the Braga substation. The results show an OCR accuracy level of around 94% on the 20 kV and 150 kV sides. Meanwhile, 92.39% on the 20 kV GFR side and 94.87% on the 150 kV side. The setting value for the pick-up current is 0.92 A on the 20 kV side of the GFR and the drop-off current is 0.85 A on the 150 kV side with a pick-up current of 0.39 A and a drop-up current of 0.37 A. Setting a value on the 20kV side is greater than on the 150 kV side due to the difference in current transformer ratio values. The simulation results show that the OCR and GFR characteristic curves on both sides meet the criteria for a protection system with good performance.