{"title":"补充氧气情况下的传导电武器火灾风险。","authors":"Jeffrey Ho, Donald M Dawes, Brian Driver","doi":"10.55460/BFZE-IKTR","DOIUrl":null,"url":null,"abstract":"<p><strong>Background: </strong>Conducted electrical weapons (CEWs) are nonlethal weapons used in tactical environments. Tactical EMS (TEMS) operators provide patient care in environments where CEWs are present. CEWs may produce a spark that can be a source of ignition. When supplemental oxygen is in use by a TEMS operator, the flammability risk from the CEW is unknown.</p><p><strong>Methods: </strong>We measured oxygen levels over 20 minutes in an enclosed space with a supplemental oxygen source maximally flowing. Measurements were taken at various distances from the oxygen source to establish baseline concentrations. These concentrations were replicated within a plexiglass box where a CEW was activated to create a sparking arc between probes embedded in a fresh swine shoulder (with skin intact). Various flammable materials, typically found in a patient care setting were used as potential fuel sources.</p><p><strong>Results: </strong>The highest oxygen levels were achieved directly at the source. At 15cm from the source, the maximum oxygen concentration was 31.5%. Within the box, ignition was only achieved at oxygen concentrations greater than 45% and only when human hair was present as fuel. No ignition was achieved at oxygen levels below this regardless of the tested fuel present.</p><p><strong>Conclusion: </strong>Ignition from a CEW is possible at supplemental oxygen levels greater than 45% when human hair is present. In an enclosed space, oxygen concentration levels of 45% are only present within 15cm of a flush rate oxygen source. The likelihood of CEW-caused ignition in such settings with supplemental oxygen in use is extremely low.</p>","PeriodicalId":53630,"journal":{"name":"Journal of special operations medicine : a peer reviewed journal for SOF medical professionals","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2024-06-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Conducted Electrical Weapon Fire Risk in the Presence of Supplemental Oxygen.\",\"authors\":\"Jeffrey Ho, Donald M Dawes, Brian Driver\",\"doi\":\"10.55460/BFZE-IKTR\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"<p><strong>Background: </strong>Conducted electrical weapons (CEWs) are nonlethal weapons used in tactical environments. Tactical EMS (TEMS) operators provide patient care in environments where CEWs are present. CEWs may produce a spark that can be a source of ignition. When supplemental oxygen is in use by a TEMS operator, the flammability risk from the CEW is unknown.</p><p><strong>Methods: </strong>We measured oxygen levels over 20 minutes in an enclosed space with a supplemental oxygen source maximally flowing. Measurements were taken at various distances from the oxygen source to establish baseline concentrations. These concentrations were replicated within a plexiglass box where a CEW was activated to create a sparking arc between probes embedded in a fresh swine shoulder (with skin intact). Various flammable materials, typically found in a patient care setting were used as potential fuel sources.</p><p><strong>Results: </strong>The highest oxygen levels were achieved directly at the source. At 15cm from the source, the maximum oxygen concentration was 31.5%. Within the box, ignition was only achieved at oxygen concentrations greater than 45% and only when human hair was present as fuel. No ignition was achieved at oxygen levels below this regardless of the tested fuel present.</p><p><strong>Conclusion: </strong>Ignition from a CEW is possible at supplemental oxygen levels greater than 45% when human hair is present. In an enclosed space, oxygen concentration levels of 45% are only present within 15cm of a flush rate oxygen source. The likelihood of CEW-caused ignition in such settings with supplemental oxygen in use is extremely low.</p>\",\"PeriodicalId\":53630,\"journal\":{\"name\":\"Journal of special operations medicine : a peer reviewed journal for SOF medical professionals\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2024-06-25\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Journal of special operations medicine : a peer reviewed journal for SOF medical professionals\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.55460/BFZE-IKTR\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q3\",\"JCRName\":\"Medicine\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of special operations medicine : a peer reviewed journal for SOF medical professionals","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.55460/BFZE-IKTR","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"Medicine","Score":null,"Total":0}
引用次数: 0

摘要

背景:导电武器(CEW)是战术环境中使用的非致命武器。战术紧急医疗服务(TEMS)操作人员在存在 CEW 的环境中为病人提供护理。CEW 可能会产生火花,成为点火源。当 TEMS 操作员使用补充氧气时,CEW 的可燃性风险尚不清楚:方法:我们在一个封闭空间内,在补充氧气源最大流量的情况下,测量了 20 分钟内的氧气水平。在距离氧气源不同的距离进行测量,以确定基准浓度。这些浓度在一个有机玻璃箱中进行复制,在该箱中启动 CEW,在嵌入新鲜猪肩(皮肤完好无损)的探针之间产生火花电弧。患者护理环境中常见的各种易燃材料被用作潜在的燃料源:直接在火源处氧气含量最高。在距离火源 15 厘米处,最高氧气浓度为 31.5%。在箱内,只有当氧气浓度高于 45% 时才能点燃,而且只有当人的头发作为燃料存在时才能点燃。无论测试的燃料是什么,当氧气浓度低于这个水平时,都无法点燃:结论:当有人类毛发存在时,在补充氧气浓度高于 45% 的情况下可以点燃 CEW。在密闭空间中,只有在距离冲洗速率氧气源 15 厘米的范围内,氧气浓度才会达到 45%。在这种使用补充氧气的环境中,由 CEW 引起点火的可能性极低。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Conducted Electrical Weapon Fire Risk in the Presence of Supplemental Oxygen.

Background: Conducted electrical weapons (CEWs) are nonlethal weapons used in tactical environments. Tactical EMS (TEMS) operators provide patient care in environments where CEWs are present. CEWs may produce a spark that can be a source of ignition. When supplemental oxygen is in use by a TEMS operator, the flammability risk from the CEW is unknown.

Methods: We measured oxygen levels over 20 minutes in an enclosed space with a supplemental oxygen source maximally flowing. Measurements were taken at various distances from the oxygen source to establish baseline concentrations. These concentrations were replicated within a plexiglass box where a CEW was activated to create a sparking arc between probes embedded in a fresh swine shoulder (with skin intact). Various flammable materials, typically found in a patient care setting were used as potential fuel sources.

Results: The highest oxygen levels were achieved directly at the source. At 15cm from the source, the maximum oxygen concentration was 31.5%. Within the box, ignition was only achieved at oxygen concentrations greater than 45% and only when human hair was present as fuel. No ignition was achieved at oxygen levels below this regardless of the tested fuel present.

Conclusion: Ignition from a CEW is possible at supplemental oxygen levels greater than 45% when human hair is present. In an enclosed space, oxygen concentration levels of 45% are only present within 15cm of a flush rate oxygen source. The likelihood of CEW-caused ignition in such settings with supplemental oxygen in use is extremely low.

求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
CiteScore
1.30
自引率
0.00%
发文量
91
期刊最新文献
Limitations of Triage in Military Mass Casualty Response: A Case Series. REBOA Use in a Medicalized Prehospital Setting Proposal for a First Protocol Based on the Delphi Method. Military Medical Student Specialty Preferences During the DHA Transition: A Retrospective Analysis. The Effect of Radiological Assessment of Volunteers for French Paratrooper Training A Five-Year Retrospective Study. Vascular Repair in Wartime Casualties.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1