{"title":"10/ 350µs冲击电流下工频连续电流的仿真研究","authors":"Xiaoming Ren, Qin Zhou","doi":"10.1109/ICHVE.2012.6357016","DOIUrl":null,"url":null,"abstract":"The paper introduced the work principle of the 10/350μs impulse current generation and analyzed the feature of the crowbar trigger circuit. Crowbar trigger circuit with 10/350μs impulse current and follow current of voltage switching type surge protective device (SPD) has been researched using EMTP simulation. In order to simulate voltage switching type SPD, the equivalent impedance of the sample and the acting time of crowbar can be obtained from test. The simulation showed that follow current trend of positive and negative polarity were almost the same under impulse of 10/ 350μs impulse current. With the same synchronous trigger angle, the initial part of follow current of SPD can be influenced due to the different polarity of impulse current.","PeriodicalId":6375,"journal":{"name":"2012 International Conference on High Voltage Engineering and Application","volume":"2009 1","pages":"141-144"},"PeriodicalIF":0.0000,"publicationDate":"2012-11-26","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Simulation studies of power frequency continuous current under 10/ 350µs impulse current tests\",\"authors\":\"Xiaoming Ren, Qin Zhou\",\"doi\":\"10.1109/ICHVE.2012.6357016\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The paper introduced the work principle of the 10/350μs impulse current generation and analyzed the feature of the crowbar trigger circuit. Crowbar trigger circuit with 10/350μs impulse current and follow current of voltage switching type surge protective device (SPD) has been researched using EMTP simulation. In order to simulate voltage switching type SPD, the equivalent impedance of the sample and the acting time of crowbar can be obtained from test. The simulation showed that follow current trend of positive and negative polarity were almost the same under impulse of 10/ 350μs impulse current. With the same synchronous trigger angle, the initial part of follow current of SPD can be influenced due to the different polarity of impulse current.\",\"PeriodicalId\":6375,\"journal\":{\"name\":\"2012 International Conference on High Voltage Engineering and Application\",\"volume\":\"2009 1\",\"pages\":\"141-144\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2012-11-26\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2012 International Conference on High Voltage Engineering and Application\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ICHVE.2012.6357016\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2012 International Conference on High Voltage Engineering and Application","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHVE.2012.6357016","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
Simulation studies of power frequency continuous current under 10/ 350µs impulse current tests
The paper introduced the work principle of the 10/350μs impulse current generation and analyzed the feature of the crowbar trigger circuit. Crowbar trigger circuit with 10/350μs impulse current and follow current of voltage switching type surge protective device (SPD) has been researched using EMTP simulation. In order to simulate voltage switching type SPD, the equivalent impedance of the sample and the acting time of crowbar can be obtained from test. The simulation showed that follow current trend of positive and negative polarity were almost the same under impulse of 10/ 350μs impulse current. With the same synchronous trigger angle, the initial part of follow current of SPD can be influenced due to the different polarity of impulse current.