{"title":"也门某民营医院建筑电气节能策略及气体减排研究与分析","authors":"عبد الجليل علي العبيدي","doi":"10.20428/JST.25.2.4","DOIUrl":null,"url":null,"abstract":"Hospital buildings consume high energy more than other buildings in the commercial buildings sector as there is a continuous demand for power  supplies. Energy consumption and greenhouse gas emissions can be reduced in the buildings sector by using various energy saving methods. In this study, on-sight visiting for energy audit has been conducted at a private hospital in Sana’a - Yemen to record all data relevant to energy consumption by equipment, machines, and all other mechanical systems. Different energy saving scenarios were using to estimate the potential of energy saving such as using high-efficiency lighting devices, raising the thermostat set point temperature for air conditioners, using high-efficiency motors (HEM) with a different load ratio, and using variable speed motors (VSM). Results indicated that energy consumption for the hospital was 4,061.8 Megawatthourper year whereas energy intensity was 232 kWh/m2. It is found that about 150.32 megawatt-hours of annual energy saving is achieved by using HEM and 689.72 Megawatt-hour per year by raising the set point of air conditioners thermostat to 26 °C. In addition, 1513 megawatt-hours per year of energy can be saved by reducing the VSM speed to 60% whereas95.8 megawatt-hours per year is estimated by adopting 100% load of HEM. The economic study of energy saving strategies was found that the use of HEM is not economically viable, while the use of VSM with large capacity motors is better from economic and environmental points of view. \nKeywords: Hospital building, energy consumption, Energy index, Energy saving, Emission reduction","PeriodicalId":21913,"journal":{"name":"Songklanakarin Journal of Science and Technology","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2021-03-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Study and Analysis of an Electrical Energy Saving Strategies and Gas Emissions Reduction for a Private Hospital Building in Yemen\",\"authors\":\"عبد الجليل علي العبيدي\",\"doi\":\"10.20428/JST.25.2.4\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Hospital buildings consume high energy more than other buildings in the commercial buildings sector as there is a continuous demand for power  supplies. Energy consumption and greenhouse gas emissions can be reduced in the buildings sector by using various energy saving methods. In this study, on-sight visiting for energy audit has been conducted at a private hospital in Sana’a - Yemen to record all data relevant to energy consumption by equipment, machines, and all other mechanical systems. Different energy saving scenarios were using to estimate the potential of energy saving such as using high-efficiency lighting devices, raising the thermostat set point temperature for air conditioners, using high-efficiency motors (HEM) with a different load ratio, and using variable speed motors (VSM). Results indicated that energy consumption for the hospital was 4,061.8 Megawatthourper year whereas energy intensity was 232 kWh/m2. It is found that about 150.32 megawatt-hours of annual energy saving is achieved by using HEM and 689.72 Megawatt-hour per year by raising the set point of air conditioners thermostat to 26 °C. In addition, 1513 megawatt-hours per year of energy can be saved by reducing the VSM speed to 60% whereas95.8 megawatt-hours per year is estimated by adopting 100% load of HEM. The economic study of energy saving strategies was found that the use of HEM is not economically viable, while the use of VSM with large capacity motors is better from economic and environmental points of view. \\nKeywords: Hospital building, energy consumption, Energy index, Energy saving, Emission reduction\",\"PeriodicalId\":21913,\"journal\":{\"name\":\"Songklanakarin Journal of Science and Technology\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2021-03-11\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Songklanakarin Journal of Science and Technology\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.20428/JST.25.2.4\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"Q3\",\"JCRName\":\"Multidisciplinary\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Songklanakarin Journal of Science and Technology","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.20428/JST.25.2.4","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"Multidisciplinary","Score":null,"Total":0}
引用次数: 0

摘要

医院建筑比其他商业建筑消耗更多的能源,因为对电力供应有持续的需求。通过采用各种节能方法,可以减少建筑物的能源消耗和温室气体排放。在本研究中,在也门萨那的一家私立医院进行了现场访问,以进行能源审计,记录设备、机器和所有其他机械系统的能源消耗相关数据。使用不同的节能方案来评估节能潜力,如使用高效照明设备、提高空调恒温器的设定点温度、使用不同负载比的高效电机(HEM)和使用变速电机(VSM)。结果表明,该医院的年能耗为4,061.8兆瓦时,而能源强度为232千瓦时/平方米。研究发现,使用HEM每年可节省约150.32兆瓦时的能源,而将空调恒温器的设定点提高至26°C,每年可节省约689.72兆瓦时的能源。此外,通过将VSM速度降低到60%,每年可节省1513兆瓦时的能源,而采用100%的HEM负荷,预计每年可节省95.8兆瓦时的能源。节能策略的经济研究发现,HEM的使用在经济上是不可行的,而VSM与大容量电机的使用从经济和环境的角度来看是更好的。关键词:医院建筑,能耗,能耗指标,节能减排
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
Study and Analysis of an Electrical Energy Saving Strategies and Gas Emissions Reduction for a Private Hospital Building in Yemen
Hospital buildings consume high energy more than other buildings in the commercial buildings sector as there is a continuous demand for power  supplies. Energy consumption and greenhouse gas emissions can be reduced in the buildings sector by using various energy saving methods. In this study, on-sight visiting for energy audit has been conducted at a private hospital in Sana’a - Yemen to record all data relevant to energy consumption by equipment, machines, and all other mechanical systems. Different energy saving scenarios were using to estimate the potential of energy saving such as using high-efficiency lighting devices, raising the thermostat set point temperature for air conditioners, using high-efficiency motors (HEM) with a different load ratio, and using variable speed motors (VSM). Results indicated that energy consumption for the hospital was 4,061.8 Megawatthourper year whereas energy intensity was 232 kWh/m2. It is found that about 150.32 megawatt-hours of annual energy saving is achieved by using HEM and 689.72 Megawatt-hour per year by raising the set point of air conditioners thermostat to 26 °C. In addition, 1513 megawatt-hours per year of energy can be saved by reducing the VSM speed to 60% whereas95.8 megawatt-hours per year is estimated by adopting 100% load of HEM. The economic study of energy saving strategies was found that the use of HEM is not economically viable, while the use of VSM with large capacity motors is better from economic and environmental points of view. Keywords: Hospital building, energy consumption, Energy index, Energy saving, Emission reduction
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
Songklanakarin Journal of Science and Technology
Songklanakarin Journal of Science and Technology Multidisciplinary-Multidisciplinary
CiteScore
1.10
自引率
0.00%
发文量
0
审稿时长
25 weeks
期刊介绍: Songklanakarin Journal of Science and Technology (SJST) aims to provide an interdisciplinary platform for the dissemination of current knowledge and advances in science and technology. Areas covered include Agricultural and Biological Sciences, Biotechnology and Agro-Industry, Chemistry and Pharmaceutical Sciences, Engineering and Industrial Research, Environmental and Natural Resources, and Physical Sciences and Mathematics. Songklanakarin Journal of Science and Technology publishes original research work, either as full length articles or as short communications, technical articles, and review articles.
期刊最新文献
The Photocatalytic Activity of Green Zinc Oxide Nanoparticles in The Treatment of Aerobically Palm Oil Mill Effluent The Usage of Banana Peels and Soybean Hull for the Treatment of Lake Water: Turbidity and Total Suspended Solids Application of Exponentially Fitted Collocation Algorithm for Solving nth-Order Fredholm Integrodifferential Equations The Economics of Network Reconfiguration and Shunt Compensation on a 33 kV Distribution Network Rheological Study of Formate (Nacl) and Ethylene Glycol Based Drilling Fluid Using MATLAB
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1