{"title":"Comparison between different procedures of reliability analysis for emergency and stand-by power systems","authors":"U. Grasselli","doi":"10.1109/ICPS.1995.527002","DOIUrl":null,"url":null,"abstract":"A general purpose Emergency Generator Set (EGS) is considered for a methodological study and related reliability behaviour is analyzed. In particular in a procedure of reliability and availability analysis of a EGS, dependent failure events need a complex mathematical model as “state-space model” to be a accurately evaluated. Furthermore these dependent failure events are one of the most important reliability characteristic of EGS. This paper suggests a procedure for reliability calculations in presence of dependent failure based on the evaluation of a equivalent failure rate that can be fitted to a network reduction method by simple mathematical calculations. The simplified models analyzed show a good accuracy for a wide range of variation of main reliability characteristics of EGS and utility. The advantages obtained are very useful on reliability evaluation because the possibility of use of network approach provides a shorter route to calculation and it is applicable by a larger number of power system designers.","PeriodicalId":138670,"journal":{"name":"Proceedings of 1995 Industrial and Commercial Power Systems Conference","volume":"188 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1995-05-07","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings of 1995 Industrial and Commercial Power Systems Conference","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICPS.1995.527002","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2
Abstract
A general purpose Emergency Generator Set (EGS) is considered for a methodological study and related reliability behaviour is analyzed. In particular in a procedure of reliability and availability analysis of a EGS, dependent failure events need a complex mathematical model as “state-space model” to be a accurately evaluated. Furthermore these dependent failure events are one of the most important reliability characteristic of EGS. This paper suggests a procedure for reliability calculations in presence of dependent failure based on the evaluation of a equivalent failure rate that can be fitted to a network reduction method by simple mathematical calculations. The simplified models analyzed show a good accuracy for a wide range of variation of main reliability characteristics of EGS and utility. The advantages obtained are very useful on reliability evaluation because the possibility of use of network approach provides a shorter route to calculation and it is applicable by a larger number of power system designers.