基于CFD模拟的大功率服务器强制对流单相浸没冷却对比研究

P. Murthy, Gautam Gupta, Joseph Herring, Jacob Lamotte-Dawaghreh, K. Sivaraju, Pratik V. Bansode, Himanshu Modi, D. Agonafer, Poornima Mynampati, Mike Sweeney
{"title":"基于CFD模拟的大功率服务器强制对流单相浸没冷却对比研究","authors":"P. Murthy, Gautam Gupta, Joseph Herring, Jacob Lamotte-Dawaghreh, K. Sivaraju, Pratik V. Bansode, Himanshu Modi, D. Agonafer, Poornima Mynampati, Mike Sweeney","doi":"10.1115/ipack2022-97402","DOIUrl":null,"url":null,"abstract":"\n Due to increasing computational workload and thermal design power requirements of high power-density microelectronics, low heat carrying capacity and poor thermal conductivity of air renders air-cooling insufficient to meet the cooling demands of component heat generation in high-performance servers. A more effective method of removing heat from these high-powered components is by using single-phase immersion cooling with a dielectric fluid of superior thermal properties and high boiling point. This study compares traditional forced-air cooling with forced convection single-phase immersion cooling to minimize chip junction temperatures of a 776 W high powered data center server using CFD simulations. The server is of spread-core configuration consisting of 2 CPU heatsink assemblies and 32 DIMM units with their specified chip thermal design power (TDPs). The first method consists of forced-air cooling with a 28°C air inlet supply and 110 CFM inlet air flowrate to establish baseline thermal performance. The second method is forced convection single-phase immersion cooling of the server in EC-110 dielectric fluid at 28 °C temperature and 2 GPM flow rate to observe server performance improvement in CPU case temperatures, maximum DIMM temperature, and server pressure drop through immersion cooling method. Lastly, CFD simulations are performed at different fluid inlet temperatures of 30, 40 and 50 °C, and 2 GPM fluid inlet flow rate, and the percentage change in the CPU case temperatures, server pressure drop and the maximum DIMM temperatures with fluid inlet temperature were studied.","PeriodicalId":117260,"journal":{"name":"ASME 2022 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-10-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"CFD Simulation-Based Comparative Study of Forced Convection Single-Phase Liquid Immersion Cooling for a High-Powered Server\",\"authors\":\"P. Murthy, Gautam Gupta, Joseph Herring, Jacob Lamotte-Dawaghreh, K. Sivaraju, Pratik V. Bansode, Himanshu Modi, D. Agonafer, Poornima Mynampati, Mike Sweeney\",\"doi\":\"10.1115/ipack2022-97402\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"\\n Due to increasing computational workload and thermal design power requirements of high power-density microelectronics, low heat carrying capacity and poor thermal conductivity of air renders air-cooling insufficient to meet the cooling demands of component heat generation in high-performance servers. A more effective method of removing heat from these high-powered components is by using single-phase immersion cooling with a dielectric fluid of superior thermal properties and high boiling point. This study compares traditional forced-air cooling with forced convection single-phase immersion cooling to minimize chip junction temperatures of a 776 W high powered data center server using CFD simulations. The server is of spread-core configuration consisting of 2 CPU heatsink assemblies and 32 DIMM units with their specified chip thermal design power (TDPs). The first method consists of forced-air cooling with a 28°C air inlet supply and 110 CFM inlet air flowrate to establish baseline thermal performance. The second method is forced convection single-phase immersion cooling of the server in EC-110 dielectric fluid at 28 °C temperature and 2 GPM flow rate to observe server performance improvement in CPU case temperatures, maximum DIMM temperature, and server pressure drop through immersion cooling method. Lastly, CFD simulations are performed at different fluid inlet temperatures of 30, 40 and 50 °C, and 2 GPM fluid inlet flow rate, and the percentage change in the CPU case temperatures, server pressure drop and the maximum DIMM temperatures with fluid inlet temperature were studied.\",\"PeriodicalId\":117260,\"journal\":{\"name\":\"ASME 2022 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems\",\"volume\":\"1 1\",\"pages\":\"0\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-10-25\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"ASME 2022 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1115/ipack2022-97402\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"ASME 2022 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1115/ipack2022-97402","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

由于高功率密度微电子的计算工作量和热设计功率要求的不断增加,空气的低热承载能力和较差的导热性使得空冷无法满足高性能服务器中组件产热的冷却需求。从这些高功率部件中去除热量的更有效方法是使用具有优异热性能和高沸点的介电流体的单相浸没冷却。本研究通过CFD模拟,比较了传统的强制空气冷却与强制对流单相浸没冷却,以最大限度地降低776 W大功率数据中心服务器的芯片结温。该服务器采用扩展核配置,由2个CPU散热器组件和32个DIMM单元组成,具有指定的芯片热设计功率(tdp)。第一种方法包括强制空气冷却,进气温度为28°C,进气流量为110 CFM,以建立基准热性能。第二种方法是将服务器置于EC-110介质中,以28℃的温度和2 GPM的流速进行强制对流单相浸没冷却,观察浸没冷却方式对服务器CPU机箱温度、DIMM最高温度、服务器压降等性能的改善。最后,在流体进口温度为30℃、40℃和50℃,流体进口流量为2 GPM的情况下进行CFD仿真,研究了CPU机箱温度、服务器压降和DIMM最高温度随流体进口温度的百分比变化。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
查看原文
分享 分享
微信好友 朋友圈 QQ好友 复制链接
本刊更多论文
CFD Simulation-Based Comparative Study of Forced Convection Single-Phase Liquid Immersion Cooling for a High-Powered Server
Due to increasing computational workload and thermal design power requirements of high power-density microelectronics, low heat carrying capacity and poor thermal conductivity of air renders air-cooling insufficient to meet the cooling demands of component heat generation in high-performance servers. A more effective method of removing heat from these high-powered components is by using single-phase immersion cooling with a dielectric fluid of superior thermal properties and high boiling point. This study compares traditional forced-air cooling with forced convection single-phase immersion cooling to minimize chip junction temperatures of a 776 W high powered data center server using CFD simulations. The server is of spread-core configuration consisting of 2 CPU heatsink assemblies and 32 DIMM units with their specified chip thermal design power (TDPs). The first method consists of forced-air cooling with a 28°C air inlet supply and 110 CFM inlet air flowrate to establish baseline thermal performance. The second method is forced convection single-phase immersion cooling of the server in EC-110 dielectric fluid at 28 °C temperature and 2 GPM flow rate to observe server performance improvement in CPU case temperatures, maximum DIMM temperature, and server pressure drop through immersion cooling method. Lastly, CFD simulations are performed at different fluid inlet temperatures of 30, 40 and 50 °C, and 2 GPM fluid inlet flow rate, and the percentage change in the CPU case temperatures, server pressure drop and the maximum DIMM temperatures with fluid inlet temperature were studied.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
期刊最新文献
AI/ML Applications for Thermally Aware SoC Designs Effects of Mechanical Cycling Induced Damage on the Creep Response of SAC305 Solder A Study on Parameters That Impact the Thermal Fatigue Life of BGA Solder Joints Experimental Investigation of the Impact of Improved Ducting and Chassis Re-Design of a Hybrid-Cooled Server Electro-Chemical Migration in Aerosol-Jet Printed Electronics Using Temperature-Humidity and Water Droplet Testing Methods
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
已复制链接
已复制链接
快去分享给好友吧!
我知道了
×
扫码分享
扫码分享
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1