首页 > 最新文献

International Journal of Civil Engineering最新文献

英文 中文
Calculation Method for Active Non-limit Earth Pressure of Cohesive Soil on a Rigid Wall Based on the Nonlinear Mohr–Coulomb Failure Criterion 基于非线性莫尔-库仑破坏准则的刚性墙上粘性土的主动非极限土压力计算方法
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-03-19 DOI: 10.1007/s40999-024-00948-3

Abstract

This work introduces a theoretical framework for determining the active non-limit earth pressure of cohesive soil on a base-rotating rigid wall. The framework incorporates the nonlinear Mohr–Coulomb failure criterion, the Duncan–Chang hyperbolic stress–strain relationship, the log-spiral potential failure surface in retained soil, and a horizontal slice method for the earth pressure evaluation. The proposed method allows quantitative determination of displacement-dependent earth pressure and its distribution along the wall back. Practical wall movement in the at-rest state is considered, and the tension crack depth near the soil surface is calculated based on the soil tensile strength cut-off. Analysis results highlight the nonlinear variation of the mobilized soil shear strength vertically, influenced by the nonlinear Mohr–Coulomb failure criterion. As the wall rotation increases, the earth pressure follows a convex parabolic distribution with a tension failure zone near the soil surface and no pressure at the wall base. The resultant of the earth pressure reduces and its application point descends while the tension crack depth expands, though always remaining less than the Rankine’s earth pressure. A practical example shows that the at-rest earth pressure can be up to 1.3 times greater than the active earth pressure, with the resultant application point approximately 5% higher. Parameter study exhibits that the active non-limit earth pressure correlates nonlinearly with the soil ultimate tensile stress and nonlinear coefficient, particularly as wall movement increases. Active non-limit earth pressures vary within 86% across different soil cohesions, and up to 50% under varying ultimate tensile stresses and nonlinear coefficients. Overturning safety factors of the wall in the active non-limit state differ significantly from those in the at-rest state, especially under varying soil cohesions.

摘要 本研究介绍了一个理论框架,用于确定粘性土对基底旋转刚性墙的主动非极限土压力。该框架结合了非线性莫尔-库仑破坏准则、邓肯-张双曲应力-应变关系、挡土的对数螺旋潜在破坏面以及土压力评估的水平切片法。所提出的方法可定量确定与位移相关的土压力及其沿墙背的分布。考虑了静止状态下的实际墙体运动,并根据土壤抗拉强度截面计算了土壤表面附近的拉伸裂缝深度。分析结果表明,受非线性莫尔-库仑失效准则的影响,土体剪切强度在垂直方向发生了非线性变化。随着墙体旋转的增加,土压力呈凸抛物线分布,在土壤表面附近有一个拉伸破坏区,而在墙基处没有压力。土压力的结果减小,其作用点下降,而拉伸裂缝深度扩大,但始终小于兰肯土压力。一个实际的例子表明,静止土压力可能是活动土压力的 1.3 倍,由此产生的作用点高出约 5%。参数研究表明,主动非极限土压力与土壤极限拉应力和非线性系数呈非线性关系,特别是随着墙体移动的增加。在不同的土壤粘聚力下,有功无限制土压力的变化在 86% 以内,而在不同的极限拉应力和非线性系数下,有功无限制土压力的变化可达 50%。主动非极限状态下的墙体倾覆安全系数与静止状态下的倾覆安全系数差别很大,尤其是在不同的土壤内聚力条件下。
{"title":"Calculation Method for Active Non-limit Earth Pressure of Cohesive Soil on a Rigid Wall Based on the Nonlinear Mohr–Coulomb Failure Criterion","authors":"","doi":"10.1007/s40999-024-00948-3","DOIUrl":"https://doi.org/10.1007/s40999-024-00948-3","url":null,"abstract":"<h3>Abstract</h3> <p>This work introduces a theoretical framework for determining the active non-limit earth pressure of cohesive soil on a base-rotating rigid wall. The framework incorporates the nonlinear Mohr–Coulomb failure criterion, the Duncan–Chang hyperbolic stress–strain relationship, the log-spiral potential failure surface in retained soil, and a horizontal slice method for the earth pressure evaluation. The proposed method allows quantitative determination of displacement-dependent earth pressure and its distribution along the wall back. Practical wall movement in the at-rest state is considered, and the tension crack depth near the soil surface is calculated based on the soil tensile strength cut-off. Analysis results highlight the nonlinear variation of the mobilized soil shear strength vertically, influenced by the nonlinear Mohr–Coulomb failure criterion. As the wall rotation increases, the earth pressure follows a convex parabolic distribution with a tension failure zone near the soil surface and no pressure at the wall base. The resultant of the earth pressure reduces and its application point descends while the tension crack depth expands, though always remaining less than the Rankine’s earth pressure. A practical example shows that the at-rest earth pressure can be up to 1.3 times greater than the active earth pressure, with the resultant application point approximately 5% higher. Parameter study exhibits that the active non-limit earth pressure correlates nonlinearly with the soil ultimate tensile stress and nonlinear coefficient, particularly as wall movement increases. Active non-limit earth pressures vary within 86% across different soil cohesions, and up to 50% under varying ultimate tensile stresses and nonlinear coefficients. Overturning safety factors of the wall in the active non-limit state differ significantly from those in the at-rest state, especially under varying soil cohesions.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"10 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-03-19","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"140169148","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Experimental Study on the Mechanical Properties of Horizontally Bolted Joints of Prefabricated Shear Walls 预制剪力墙水平螺栓连接力学性能的实验研究
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-03-18 DOI: 10.1007/s40999-024-00946-5
Yong Xu, Yujie Fan, Yingda Zhang, Bo Shu, Hongyuan Tang

Based on the existing research results on prefabricated shear wall vertical bolt connections, the force performance of horizontal bolt joints composed of multiple bolt connections were further examined in this paper. Through the quasistatic load test of two horizontal bolt joint specimens, the hysteresis curve, backbone curve, and stiffness degradation curve of the wall were obtained. The test results show that the specimens’ load-bearing capacity can reach 240–280 kN, with a maximum displacement between 40 and 70 mm, indicating that the force performance and deformation ability of the horizontal joint are good at this size. The overall shape of the hysteretic curve of the specimens is similar to an arch, with a certain pinch effect, and the hysteretic loop is relatively full, indicating good energy dissipation ability. The failure of the specimens reveals that a single bolt connection exists under shear, compression and tension conditions. The force state of the bolt connections in the horizontal joints was divided into four situations: shear state, axial compression state, small eccentric compression state and large eccentric compression state. For each situation, a calculation formula for bolt connections in horizontal joints was proposed and the average relative error is 4.72%, providing a reference for the force calculation of this type of joint.

在已有的预制剪力墙垂直螺栓连接研究成果的基础上,本文进一步研究了由多个螺栓连接组成的水平螺栓连接的受力性能。通过对两个水平螺栓连接试件进行静载试验,得到了墙体的滞后曲线、骨干曲线和刚度衰减曲线。试验结果表明,试件的承载力可达 240-280 kN,最大位移在 40-70 mm 之间,表明水平接头在此尺寸下的受力性能和变形能力良好。试件的滞回曲线整体形状类似于拱形,具有一定的夹角效应,滞回环路比较饱满,说明消能能力较好。试件的破坏表明,在剪切、压缩和拉伸条件下都存在单一的螺栓连接。水平连接中螺栓连接的受力状态分为四种情况:剪切状态、轴向压缩状态、小偏心压缩状态和大偏心压缩状态。针对每种情况,提出了水平连接中螺栓连接的计算公式,其平均相对误差为 4.72%,为这类连接的受力计算提供了参考。
{"title":"Experimental Study on the Mechanical Properties of Horizontally Bolted Joints of Prefabricated Shear Walls","authors":"Yong Xu, Yujie Fan, Yingda Zhang, Bo Shu, Hongyuan Tang","doi":"10.1007/s40999-024-00946-5","DOIUrl":"https://doi.org/10.1007/s40999-024-00946-5","url":null,"abstract":"<p>Based on the existing research results on prefabricated shear wall vertical bolt connections, the force performance of horizontal bolt joints composed of multiple bolt connections were further examined in this paper. Through the quasistatic load test of two horizontal bolt joint specimens, the hysteresis curve, backbone curve, and stiffness degradation curve of the wall were obtained. The test results show that the specimens’ load-bearing capacity can reach 240–280 kN, with a maximum displacement between 40 and 70 mm, indicating that the force performance and deformation ability of the horizontal joint are good at this size. The overall shape of the hysteretic curve of the specimens is similar to an arch, with a certain pinch effect, and the hysteretic loop is relatively full, indicating good energy dissipation ability. The failure of the specimens reveals that a single bolt connection exists under shear, compression and tension conditions. The force state of the bolt connections in the horizontal joints was divided into four situations: shear state, axial compression state, small eccentric compression state and large eccentric compression state. For each situation, a calculation formula for bolt connections in horizontal joints was proposed and the average relative error is 4.72%, providing a reference for the force calculation of this type of joint.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"39 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-03-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"140169292","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Seismic Performance and Damage Mechanism of RC Double-Column Pier Structure with Triple Coupling Beams 带三重耦合梁的钢筋混凝土双柱墩结构的抗震性能和破坏机理
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-03-18 DOI: 10.1007/s40999-024-00945-6
Wenhao Feng, Zhongwen Zhang, Jianxing Sun, Mengyao Ci, Shaojie Wang

Coupling beams are used in double-column high-pier bridges to improve the integrity of the two piers. The stiffness of coupling beams has a significant effect on the seismic performance of double-column piers. The seismic behavior of a double-column pier with triple-coupled beams was investigated by cyclic loading test. The failure mode and cyclic response, as well as the shear deformation of a double-column bridge pier, were analyzed to investigate its seismic behavior. The test results, especially after a drift ratio of 1/83, indicated the presence of non-uniform damage characteristics between the coupling beams. Finite element models were developed and parametric analysis was carried out after validation. The focus was on the effects of the variable stiffness of the coupling beam along its height. By analyzing the bearing capacity, ductility, and damage of the double-column piers, the upper flexible and lower rigid coupling beam is a more reasonable arrangement principle. The research results can provide a reference for the innovation design ideas of similar bridge piers.

联梁用于双柱高墩桥梁,以提高两个桥墩的整体性。耦合梁的刚度对双柱桥墩的抗震性能有很大影响。通过循环加载试验研究了带有三重耦合梁的双柱桥墩的抗震性能。分析了双柱桥墩的破坏模式和周期响应以及剪切变形,以研究其抗震行为。试验结果,尤其是在漂移比为 1/83 之后,表明耦合梁之间存在非均匀破坏特征。开发了有限元模型,并在验证后进行了参数分析。重点是耦合梁沿高度的不同刚度的影响。通过分析双柱墩的承载力、延性和破坏情况,发现上柔下刚的耦合梁是一种较为合理的布置原则。研究成果可为类似桥墩的创新设计思路提供参考。
{"title":"Seismic Performance and Damage Mechanism of RC Double-Column Pier Structure with Triple Coupling Beams","authors":"Wenhao Feng, Zhongwen Zhang, Jianxing Sun, Mengyao Ci, Shaojie Wang","doi":"10.1007/s40999-024-00945-6","DOIUrl":"https://doi.org/10.1007/s40999-024-00945-6","url":null,"abstract":"<p>Coupling beams are used in double-column high-pier bridges to improve the integrity of the two piers. The stiffness of coupling beams has a significant effect on the seismic performance of double-column piers. The seismic behavior of a double-column pier with triple-coupled beams was investigated by cyclic loading test. The failure mode and cyclic response, as well as the shear deformation of a double-column bridge pier, were analyzed to investigate its seismic behavior. The test results, especially after a drift ratio of 1/83, indicated the presence of non-uniform damage characteristics between the coupling beams. Finite element models were developed and parametric analysis was carried out after validation. The focus was on the effects of the variable stiffness of the coupling beam along its height. By analyzing the bearing capacity, ductility, and damage of the double-column piers, the upper flexible and lower rigid coupling beam is a more reasonable arrangement principle. The research results can provide a reference for the innovation design ideas of similar bridge piers.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"20 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-03-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"140169737","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Mechanical Performance of Welded–Bolted Hybrid Connection Joints Between Fire-Resistant Steel Columns and Beams Under Fire 耐火钢柱和钢梁之间的焊接-栓接混合连接接头在火灾中的机械性能
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-03-18 DOI: 10.1007/s40999-024-00952-7

Abstract

The mechanical properties of connection joints and the fire protection design of steel structures are crucial for ensuring structural safety. The utilization of fire-resistant steel in steel structure joints represents a novel approach to enhance fire resistance. In this study, a test on two welded–bolted hybrid connection joints between fire-resistant steel columns and beams was conducted considering both ambient and elevated temperatures. Through an analysis of the failure modes, load–vertical displacement curves, moment–rotation curves, and load–strain curves of the joints, key parameters such as the ultimate bearing capacity, ductility, and deformation capacity were determined. The test results showed that the ultimate bearing capacity of specimen Joint-2-ET at an elevated temperature is 81.14% that of specimen Joint-1-AT at an ambient temperature. While the temperature increases during fire had little effect on the initial stiffness of the joint, it significantly reduced the rotation capacity and ductility of the joint. A finite element model of the joints was developed using ABAQUS software, and its accuracy was validated by comparing the results with the experimental findings. Additionally, a parametric analysis was conducted to explore the effects of temperature and heating region on the mechanical performance of these welded–bolted hybrid connection joints. The outcomes of this research provide valuable insights for engineering applications involving welded–bolted hybrid connection joints between fire-resistant steel columns and beams.

摘要 钢结构连接接头的机械性能和防火设计对于确保结构安全至关重要。在钢结构连接处使用耐火钢是提高耐火性的一种新方法。在本研究中,对耐火钢柱和梁之间的两个焊接-螺栓混合连接接头进行了测试,测试同时考虑了环境温度和高温。通过分析接头的失效模式、荷载-垂直位移曲线、力矩-旋转曲线和荷载-应变曲线,确定了极限承载能力、延展性和变形能力等关键参数。试验结果表明,试样 Joint-2-ET 在高温下的极限承载能力是试样 Joint-1-AT 在常温下的 81.14%。虽然火灾期间温度的升高对接头的初始刚度影响不大,但却大大降低了接头的旋转能力和延展性。使用 ABAQUS 软件建立了接头的有限元模型,并通过将结果与实验结果进行比较,验证了模型的准确性。此外,还进行了参数分析,以探讨温度和加热区域对这些焊接-螺栓混合连接接头机械性能的影响。这项研究成果为涉及耐火钢柱和钢梁之间焊接-螺栓混合连接接头的工程应用提供了宝贵的见解。
{"title":"Mechanical Performance of Welded–Bolted Hybrid Connection Joints Between Fire-Resistant Steel Columns and Beams Under Fire","authors":"","doi":"10.1007/s40999-024-00952-7","DOIUrl":"https://doi.org/10.1007/s40999-024-00952-7","url":null,"abstract":"<h3>Abstract</h3> <p>The mechanical properties of connection joints and the fire protection design of steel structures are crucial for ensuring structural safety. The utilization of fire-resistant steel in steel structure joints represents a novel approach to enhance fire resistance. In this study, a test on two welded–bolted hybrid connection joints between fire-resistant steel columns and beams was conducted considering both ambient and elevated temperatures. Through an analysis of the failure modes, load–vertical displacement curves, moment–rotation curves, and load–strain curves of the joints, key parameters such as the ultimate bearing capacity, ductility, and deformation capacity were determined. The test results showed that the ultimate bearing capacity of specimen Joint-2-ET at an elevated temperature is 81.14% that of specimen Joint-1-AT at an ambient temperature. While the temperature increases during fire had little effect on the initial stiffness of the joint, it significantly reduced the rotation capacity and ductility of the joint. A finite element model of the joints was developed using ABAQUS software, and its accuracy was validated by comparing the results with the experimental findings. Additionally, a parametric analysis was conducted to explore the effects of temperature and heating region on the mechanical performance of these welded–bolted hybrid connection joints. The outcomes of this research provide valuable insights for engineering applications involving welded–bolted hybrid connection joints between fire-resistant steel columns and beams.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"90 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-03-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"140169150","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Structural Performance of Cold Formed Steel Composite Beams with Profiled Steel Sheeting 带有异型钢板的冷成型钢复合梁的结构性能
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-03-18 DOI: 10.1007/s40999-024-00949-2
Ahmad Karimipanah, Mehran Zeynalian, Abdolreza Ataei

This study presents an experimental study on cold-formed steel (CFS) composite beams with profiled steel sheeting. Four full-scale composite beam specimens comprising cold-formed double-lipped channel sections, profiled steel sheeting, concrete slabs, and bolted shear connectors were examined. The results show that profiled steel sheeting behaves like tensile reinforcement beside the concrete slab. Of particular interests were thickness and height of CFS beams. The results showed that for higher steel thickness, the failure mode was concrete crushing before CFS beam reached its yielding point. Besides, no failure occurred in the shear connections. By increasing the thickness of CFS from 1.25 to 2 mm, the ultimate loading capacity of composite beams increased almost 45%. This was due to the presence of the profiled steel sheeting and the strong connectors, which prevented sudden slip between the CFS beam and the concrete slab. A comparison between code-calculated and experimentally evaluated degree of shear connection shows that the results are so close. Furthermore, a 3D finite element model was established, and the numerical models were verified against experimental results and the behavior of structures were accurately simulated.

本研究介绍了对带有异型钢板的冷弯型钢(CFS)复合梁的实验研究。研究考察了四个全尺寸复合梁试件,包括冷弯双唇槽型钢、异型钢板、混凝土板和螺栓剪力连接件。结果表明,异型钢板与混凝土板旁的抗拉钢筋表现相似。特别值得关注的是 CFS 梁的厚度和高度。结果表明,钢板厚度越大,在 CFS 梁达到屈服点之前,其破坏模式是混凝土破碎。此外,在剪力连接处没有发生破坏。将 CFS 厚度从 1.25 毫米增加到 2 毫米后,复合梁的极限承载能力提高了近 45%。这归功于异型钢板和坚固的连接件,它们防止了 CFS 梁和混凝土板之间的突然滑移。通过比较规范计算和实验评估的剪力连接程度,可以看出结果非常接近。此外,还建立了三维有限元模型,并根据实验结果对数值模型进行了验证,准确模拟了结构的行为。
{"title":"Structural Performance of Cold Formed Steel Composite Beams with Profiled Steel Sheeting","authors":"Ahmad Karimipanah, Mehran Zeynalian, Abdolreza Ataei","doi":"10.1007/s40999-024-00949-2","DOIUrl":"https://doi.org/10.1007/s40999-024-00949-2","url":null,"abstract":"<p>This study presents an experimental study on cold-formed steel (CFS) composite beams with profiled steel sheeting. Four full-scale composite beam specimens comprising cold-formed double-lipped channel sections, profiled steel sheeting, concrete slabs, and bolted shear connectors were examined. The results show that profiled steel sheeting behaves like tensile reinforcement beside the concrete slab. Of particular interests were thickness and height of CFS beams. The results showed that for higher steel thickness, the failure mode was concrete crushing before CFS beam reached its yielding point. Besides, no failure occurred in the shear connections. By increasing the thickness of CFS from 1.25 to 2 mm, the ultimate loading capacity of composite beams increased almost 45%. This was due to the presence of the profiled steel sheeting and the strong connectors, which prevented sudden slip between the CFS beam and the concrete slab. A comparison between code-calculated and experimentally evaluated degree of shear connection shows that the results are so close. Furthermore, a 3D finite element model was established, and the numerical models were verified against experimental results and the behavior of structures were accurately simulated.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"17 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-03-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"140169288","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Using Retractable Baffle-Type Rectangular Pipe Jacking for the Construction of a Tunnel with a Large Cross-Section in a Complex Environment 使用可伸缩挡板式矩形顶管在复杂环境中建造大断面隧道
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-03-03 DOI: 10.1007/s40999-023-00932-3
Li Tang, Zhiqiang Zhang

In this study, we propose baffle-type rectangular pipe jacking in the context of the world’s first shallow large-section rectangular pipe-jacking project under a high-speed railway line, with the aim of improving the utilization of underground urban space. We introduce the relevant method of construction as well as safety control technology for ongoing construction in the proximity of pipe jacking in a complex geological and structural environment, and propose techniques of optimization for the continued application of baffle-type rectangular pipe jacking in similar projects. The results showed the following: (1) the maximum value of the surface settlement as the pipe-jacking machine passed through it was 160 mm. But the maximum uplift, maximum settlement, and maximum relative settlement of the D-shape temporary beams were 6.31, −5.78, and 6.71 mm. (2) The theoretical mechanics-based calculations was used to derive the minimum safe distance required to form a stable microarch effect between the roofs of the pipes, and the recommended distance in the project considered in this study was 24 cm. (3) The results of assessments based on multiple measures showed that the proposed pipe-jacking method led to the successful completion of crossing work for high-speed rails that were in use. This means that it is feasible to use rectangular pipe jacking to pass through an operating high-speed rail in composite strata at a shallow depth. We also provide suggestions for applications of the retractable baffle-type rectangular pipe jacking in the future.

在本研究中,我们结合世界首例高速铁路线下浅埋大断面矩形顶管工程,提出了挡板式矩形顶管技术,旨在提高城市地下空间的利用率。我们介绍了在复杂地质和结构环境下进行顶管临近施工的相关施工方法和安全控制技术,并提出了在类似工程中继续应用挡板式矩形顶管的优化技术。研究结果表明(1)顶管机通过地表时,地表沉降的最大值为 160 毫米。但 D 型临时梁的最大隆起、最大沉降和最大相对沉降分别为 6.31、-5.78 和 6.71 毫米。(2) 通过基于理论力学的计算,得出了在管道顶之间形成稳定的微拱效应所需的最小安全距离,在本研究考虑的项目中,建议距离为 24 厘米。(3) 基于多种措施的评估结果表明,建议的顶管方法成功完成了正在使用的高速铁路的穿越工作。这说明,在复合地层中使用矩形顶管穿越运行中的高速铁路浅层是可行的。我们还对可伸缩挡板式矩形顶管在未来的应用提出了建议。
{"title":"Using Retractable Baffle-Type Rectangular Pipe Jacking for the Construction of a Tunnel with a Large Cross-Section in a Complex Environment","authors":"Li Tang, Zhiqiang Zhang","doi":"10.1007/s40999-023-00932-3","DOIUrl":"https://doi.org/10.1007/s40999-023-00932-3","url":null,"abstract":"<p>In this study, we propose baffle-type rectangular pipe jacking in the context of the world’s first shallow large-section rectangular pipe-jacking project under a high-speed railway line, with the aim of improving the utilization of underground urban space. We introduce the relevant method of construction as well as safety control technology for ongoing construction in the proximity of pipe jacking in a complex geological and structural environment, and propose techniques of optimization for the continued application of baffle-type rectangular pipe jacking in similar projects. The results showed the following: (1) the maximum value of the surface settlement as the pipe-jacking machine passed through it was 160 mm. But the maximum uplift, maximum settlement, and maximum relative settlement of the D-shape temporary beams were 6.31, −5.78, and 6.71 mm. (2) The theoretical mechanics-based calculations was used to derive the minimum safe distance required to form a stable microarch effect between the roofs of the pipes, and the recommended distance in the project considered in this study was 24 cm. (3) The results of assessments based on multiple measures showed that the proposed pipe-jacking method led to the successful completion of crossing work for high-speed rails that were in use. This means that it is feasible to use rectangular pipe jacking to pass through an operating high-speed rail in composite strata at a shallow depth. We also provide suggestions for applications of the retractable baffle-type rectangular pipe jacking in the future.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"319 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-03-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"140026060","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
An Optimization Model to Address the Skilled Labor Shortage in the Construction Industry 解决建筑业技术工人短缺问题的优化模型
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-02-29 DOI: 10.1007/s40999-024-00941-w
Olawale Adekunle, Manoj K. Jha

An optimization problem is formulated in this study to optimize the total investment in education, apprenticeship, and financial incentive to address the skilled labor shortages in the construction industry. Three separate mathematical models, namely linear programming (LP) models, fuzzy mathematical models, and structural equation models are compared for their accuracy, robustness, and ease of application in solving the optimization problem. LP models are found to be the best fit for solving the optimization problem. Relevant data on construction budget and investment preferences in education, apprenticeship, and financial incentive are obtained through a survey questionnaire from construction firms engaged in commercial and residential construction. The survey response suggests that more apprentices lean toward electrical and plumbing over carpentry due to the higher pay scale in both trade fields, thus reducing the skilled labor shortage in both areas when compared to carpentry. The optimization results indicate that apprenticeship and financial incentives play a significant role in reducing short-term labor shortages. Education, on the other hand, plays a significant role in reducing the labor shortage in the long run. A sensitivity analysis shows different optimal investments for the optimal allocation of labor shortages to be overcome by investments in education, apprenticeship, and financial incentives. A more robust analysis using additional data can be performed in future works to further investigate the relative effectiveness of investments in education, apprenticeship, and financial incentives in reducing skilled labor shortage.

本研究提出了一个优化问题,以优化在教育、学徒制和财政激励方面的总投资,从而解决建筑业技术工人短缺的问题。比较了三种不同的数学模型,即线性规划(LP)模型、模糊数学模型和结构方程模型在解决优化问题时的准确性、稳健性和易用性。结果发现,LP 模型最适合解决优化问题。通过对从事商业和住宅建设的建筑公司进行问卷调查,获得了有关建筑预算以及在教育、学徒制和经济激励方面的投资偏好的相关数据。调查结果表明,与木工相比,更多的学徒倾向于电气和管道工,因为这两个工种的薪资水平较高,从而减少了这两个领域的技工短缺。优化结果表明,学徒制和经济激励措施在减少短期劳动力短缺方面发挥了重要作用。另一方面,从长远来看,教育在减少劳动力短缺方面发挥着重要作用。一项敏感性分析表明,教育、学徒制和经济激励机制的投资对克服劳动力短缺的最优配置具有不同的最优投资效果。在今后的工作中,可以利用更多数据进行更稳健的分析,进一步研究教育投资、学徒制投资和经济激励措施在减少熟练劳动力短缺方面的相对效果。
{"title":"An Optimization Model to Address the Skilled Labor Shortage in the Construction Industry","authors":"Olawale Adekunle, Manoj K. Jha","doi":"10.1007/s40999-024-00941-w","DOIUrl":"https://doi.org/10.1007/s40999-024-00941-w","url":null,"abstract":"<p>An optimization problem is formulated in this study to optimize the total investment in education, apprenticeship, and financial incentive to address the skilled labor shortages in the construction industry. Three separate mathematical models, namely linear programming (LP) models, fuzzy mathematical models, and structural equation models are compared for their accuracy, robustness, and ease of application in solving the optimization problem. LP models are found to be the best fit for solving the optimization problem. Relevant data on construction budget and investment preferences in education, apprenticeship, and financial incentive are obtained through a survey questionnaire from construction firms engaged in commercial and residential construction. The survey response suggests that more apprentices lean toward electrical and plumbing over carpentry due to the higher pay scale in both trade fields, thus reducing the skilled labor shortage in both areas when compared to carpentry. The optimization results indicate that apprenticeship and financial incentives play a significant role in reducing short-term labor shortages. Education, on the other hand, plays a significant role in reducing the labor shortage in the long run. A sensitivity analysis shows different optimal investments for the optimal allocation of labor shortages to be overcome by investments in education, apprenticeship, and financial incentives. A more robust analysis using additional data can be performed in future works to further investigate the relative effectiveness of investments in education, apprenticeship, and financial incentives in reducing skilled labor shortage.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"21 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-02-29","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"140009193","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Mix Design Method for Coating Mixed Mortar According to Influence of the Aggregate Type and Application Environment Conditions 根据骨料类型和应用环境条件的影响确定涂层混合砂浆的混合设计方法
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-02-26 DOI: 10.1007/s40999-024-00942-9
Rodrigo Bayão Salgado Leão, Reginaldo Carneiro da Silva, Leonardo Gonçalves Pedrotti, White José dos Santos

No recent research was found regarding mix design for coating mortars. Those that exist (older ones) have limitations in use or specific materials. They are defined for the use of a certain equipment or specific condition and cannot be applied in other regions. An appropriate mix project needs to have a process that al-lows to obtain adequate proportions of the materials taking into account the different materials and conditions at the application site. Therefore, the aim of this paper is to propose an experimental mix design method for mixed mortars to be used in wall cladding and to study two types of most common aggregates (natural or crushing) through properties from the application sites and material characteristics. The experimental program of this study consisted in characterizing the materials and conducting necessary tests to evaluate the mix design method and how the characteristics of the aggregates influence the mixing design process, as well as the mechanical properties (flexural, compressive strength and pull off strength) and durability indicators (elasticity modulus, water absorption and porosity). We verified that the characteristics of the aggregates interfere with the properties of these composites and that the proposed method was able to capture this and define adequate proportions of the materials according to the exposure conditions. The method generated more economical (less cement consumption) and more sustainable mixed coating mor-tars (reduction of cement and lime in the mixtures, especially with artificial aggregate) without compromising the limiting properties Pull Off (0.390 MPa) and Flexural Strength (2.396 MPa). We conclude that the mix design method allows to optimize the characteristics of the mixed mortars depending on the type/characteristics of the aggregate and the conditions of the application environment.

关于涂料砂浆的混合设计,没有发现最新的研究成果。现有的研究(较早的研究)在使用或特定材料方面都有限制。它们是为使用某种设备或特定条件而定义的,不能用于其他地区。适当的混合项目需要有一个过程,以便在考虑到不同材料和应用现场条件的情况下获得适当的材料比例。因此,本文的目的是为墙面覆盖层中使用的混合砂浆提出一种实验混合设计方法,并通过应用地点和材料特性的属性研究两种最常见的集料(天然集料或破碎集料)。这项研究的实验项目包括确定材料特性和进行必要的测试,以评估混合设计方法、骨料特性如何影响混合设计过程、机械特性(抗弯强度、抗压强度和抗拉强度)和耐久性指标(弹性模量、吸水性和孔隙率)。我们证实,骨料的特性会影响这些复合材料的性能,而所提出的方法能够捕捉到这一点,并根据暴露条件确定适当的材料比例。该方法能产生更经济(更少的水泥用量)和更可持续的混合涂料(减少混合物中的水泥和石灰用量,尤其是人工骨料),同时不影响极限性能拉断强度(0.390 兆帕)和挠曲强度(2.396 兆帕)。我们的结论是,根据骨料的类型/特性和应用环境条件,混合设计方法可以优化混合砂浆的特性。
{"title":"Mix Design Method for Coating Mixed Mortar According to Influence of the Aggregate Type and Application Environment Conditions","authors":"Rodrigo Bayão Salgado Leão, Reginaldo Carneiro da Silva, Leonardo Gonçalves Pedrotti, White José dos Santos","doi":"10.1007/s40999-024-00942-9","DOIUrl":"https://doi.org/10.1007/s40999-024-00942-9","url":null,"abstract":"<p>No recent research was found regarding mix design for coating mortars. Those that exist (older ones) have limitations in use or specific materials. They are defined for the use of a certain equipment or specific condition and cannot be applied in other regions. An appropriate mix project needs to have a process that al-lows to obtain adequate proportions of the materials taking into account the different materials and conditions at the application site. Therefore, the aim of this paper is to propose an experimental mix design method for mixed mortars to be used in wall cladding and to study two types of most common aggregates (natural or crushing) through properties from the application sites and material characteristics. The experimental program of this study consisted in characterizing the materials and conducting necessary tests to evaluate the mix design method and how the characteristics of the aggregates influence the mixing design process, as well as the mechanical properties (flexural, compressive strength and pull off strength) and durability indicators (elasticity modulus, water absorption and porosity). We verified that the characteristics of the aggregates interfere with the properties of these composites and that the proposed method was able to capture this and define adequate proportions of the materials according to the exposure conditions. The method generated more economical (less cement consumption) and more sustainable mixed coating mor-tars (reduction of cement and lime in the mixtures, especially with artificial aggregate) without compromising the limiting properties Pull Off (0.390 MPa) and Flexural Strength (2.396 MPa). We conclude that the mix design method allows to optimize the characteristics of the mixed mortars depending on the type/characteristics of the aggregate and the conditions of the application environment.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"18 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-02-26","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"139977705","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Study on the Influence of Blasting Construction of Double-Layer Superimposed Primary Support Arch Cover Method on the Surrounding Environment 双层叠加一级支撑拱盖法爆破施工对周边环境的影响研究
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-02-15 DOI: 10.1007/s40999-024-00939-4
Xinping Guo, Annan Jiang, Qinghua Min

To study the impact of blasting construction of double-layer superimposed primary support arch cover method, relying on the station construction project of Dalian Metro Line 5, the disturbance of blasting on high-rise buildings, surrounding strata, adjacent pilot tunnels and the arch structure is analyzed based on numerical simulation and field monitoring results. At the same time, research is carried out on the blasting excavation footage of pilot tunnels. The results show that there will be a certain “elevation amplification effect” (EAE) on high-rise buildings during the blasting construction using the method. The peak particle velocity (PPV) of adjacent tunnels decreases gradually with the increase of the distance from the explosion centers. For the adjacent pilot tunnel, the main influence area is within the range of − 5 to 5 m from the pilot tunnel face. For adjacent buildings, the main influence stage is within the range of − 2 to 2 m from the pilot tunnel face. Blasting operations significantly intensify the plastic yield of surrounding rocks around the station. Blasting excavation footage can be used as the optimization parameter in the construction process, and the blasting excavation footage of pilot tunnel 4 can be adjusted from 1.0 to 1.5 m. The formation of the arch structure composed of double-layer superimposed primary support and secondary lining effectively reduces the impact of rock blasting on the whole station and high-rise buildings.

以大连地铁 5 号线车站建设工程为依托,研究双层叠合一次支护拱盖法爆破施工的影响,基于数值模拟和现场监测结果,分析爆破对高层建筑、周边地层、相邻试验隧道及拱结构的扰动。同时,还对试验隧道的爆破开挖进尺进行了研究。结果表明,使用该方法进行爆破施工时,会对高层建筑产生一定的 "高程放大效应"(EAE)。相邻隧道的峰值颗粒速度(PPV)随着与爆心距离的增加而逐渐减小。对于邻近的先导隧道,主要影响区域在距先导隧道面-5 至 5 米的范围内。对于相邻的建筑物,主要影响范围在距先导隧道面 - 2 至 2 m 的范围内。爆破作业会大大提高车站周围岩石的塑性产状。爆破开挖进尺可作为施工过程中的优化参数,先导隧道 4 的爆破开挖进尺可在 1.0 至 1.5 米范围内调整。
{"title":"Study on the Influence of Blasting Construction of Double-Layer Superimposed Primary Support Arch Cover Method on the Surrounding Environment","authors":"Xinping Guo, Annan Jiang, Qinghua Min","doi":"10.1007/s40999-024-00939-4","DOIUrl":"https://doi.org/10.1007/s40999-024-00939-4","url":null,"abstract":"<p>To study the impact of blasting construction of double-layer superimposed primary support arch cover method, relying on the station construction project of Dalian Metro Line 5, the disturbance of blasting on high-rise buildings, surrounding strata, adjacent pilot tunnels and the arch structure is analyzed based on numerical simulation and field monitoring results. At the same time, research is carried out on the blasting excavation footage of pilot tunnels. The results show that there will be a certain “elevation amplification effect” (EAE) on high-rise buildings during the blasting construction using the method. The peak particle velocity (PPV) of adjacent tunnels decreases gradually with the increase of the distance from the explosion centers. For the adjacent pilot tunnel, the main influence area is within the range of − 5 to 5 m from the pilot tunnel face. For adjacent buildings, the main influence stage is within the range of − 2 to 2 m from the pilot tunnel face. Blasting operations significantly intensify the plastic yield of surrounding rocks around the station. Blasting excavation footage can be used as the optimization parameter in the construction process, and the blasting excavation footage of pilot tunnel 4 can be adjusted from 1.0 to 1.5 m. The formation of the arch structure composed of double-layer superimposed primary support and secondary lining effectively reduces the impact of rock blasting on the whole station and high-rise buildings.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"34 1","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-02-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"139771763","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
Study on Acoustic Emission and Crack Propagation Characteristics of Single-Fissured Sandstone with Different Angles Under Uniaxial Compression 单轴压缩下不同角度单裂砂岩的声发射和裂缝扩展特性研究
IF 1.7 4区 工程技术 Q3 ENGINEERING, CIVIL Pub Date : 2024-02-15 DOI: 10.1007/s40999-024-00940-x
Jia-Qi Guo, Zi-Hui Zhu, Jian-Xun Chen, Fei-Yue Sun, Zheng Wang

The uniaxial compression tests are conducted on single-fissured sandstone with different angles, and the effect of fissure angle (β) on mechanical properties, acoustic emission (AE) features, crack propagation characteristics, and failure mode of sandstone are studied with the AE monitoring and photographic system. The research results reveal that as the β increases, the uniaxial compressive strength (UCS) exhibits an asymmetric inverted “U” shape and the minimum is only 33.14 MPa when β = 30°, while the elastic modulus increases monotonously from 8.98 to 15.14 GPa. During the loading process, the AE parameters demonstrate obvious stage characteristics, while tension cracks dominate and the shear cracks significantly increase. As β increases, the AE activity gradually shifts to the post-peak destruction stage, and the effect of shear crack on the final failure mode of the specimens becomes more significant. The stress–strain relationship, AE features, and real-time photographic system are sufficient to comprehensively depict the crack evolution process in each stage, and there is a good correlation between each parameter. Increase in β makes the crack initiation stress and its ratio to UCS increase, from 68.74% to 79.92%, which makes it more difficult for crack initiation, and the secondary crack propagation gradually transforms from tension to shear. The macroscopic failure mode of fissured sandstone gradually changes from tension failure to mixed tension–shear failure and finally to shear failure, the angle between the propagation direction of initial cracks and fissure gradually decreases, and the surface spalling zone becomes more obvious.

对不同角度的单发砂岩进行了单轴压缩试验,利用声发射监测和照相系统研究了裂隙角度(β)对砂岩力学性能、声发射(AE)特征、裂纹扩展特征和破坏模式的影响。研究结果表明,随着 β 的增大,单轴抗压强度(UCS)呈现不对称的倒 "U "形,当 β = 30° 时,最小值仅为 33.14 MPa,而弹性模量则从 8.98 GPa 单调增加到 15.14 GPa。在加载过程中,AE 参数表现出明显的阶段性特征,拉伸裂纹占主导地位,剪切裂纹显著增加。随着 β 的增大,AE 活动逐渐转向峰值破坏后阶段,剪切裂纹对试样最终破坏模式的影响变得更加显著。应力应变关系、AE 特征和实时摄影系统足以全面描述各阶段的裂纹演变过程,且各参数之间具有良好的相关性。β 的增大使裂纹萌生应力及其与 UCS 的比值增大,从 68.74% 增大到 79.92%,增加了裂纹萌生的难度,二次裂纹扩展逐渐由拉伸向剪切转变。裂缝砂岩的宏观破坏模式逐渐从拉伸破坏转变为拉伸-剪切混合破坏,最后转变为剪切破坏,初始裂缝的扩展方向与裂缝之间的夹角逐渐减小,表面剥落带变得更加明显。
{"title":"Study on Acoustic Emission and Crack Propagation Characteristics of Single-Fissured Sandstone with Different Angles Under Uniaxial Compression","authors":"Jia-Qi Guo, Zi-Hui Zhu, Jian-Xun Chen, Fei-Yue Sun, Zheng Wang","doi":"10.1007/s40999-024-00940-x","DOIUrl":"https://doi.org/10.1007/s40999-024-00940-x","url":null,"abstract":"<p>The uniaxial compression tests are conducted on single-fissured sandstone with different angles, and the effect of fissure angle (<i>β</i>) on mechanical properties, acoustic emission (AE) features, crack propagation characteristics, and failure mode of sandstone are studied with the AE monitoring and photographic system. The research results reveal that as the <i>β</i> increases, the uniaxial compressive strength (UCS) exhibits an asymmetric inverted “U” shape and the minimum is only 33.14 MPa when <i>β</i> = 30°, while the elastic modulus increases monotonously from 8.98 to 15.14 GPa. During the loading process, the AE parameters demonstrate obvious stage characteristics, while tension cracks dominate and the shear cracks significantly increase. As <i>β</i> increases, the AE activity gradually shifts to the post-peak destruction stage, and the effect of shear crack on the final failure mode of the specimens becomes more significant. The stress–strain relationship, AE features, and real-time photographic system are sufficient to comprehensively depict the crack evolution process in each stage, and there is a good correlation between each parameter. Increase in <i>β</i> makes the crack initiation stress and its ratio to UCS increase, from 68.74% to 79.92%, which makes it more difficult for crack initiation, and the secondary crack propagation gradually transforms from tension to shear. The macroscopic failure mode of fissured sandstone gradually changes from tension failure to mixed tension–shear failure and finally to shear failure, the angle between the propagation direction of initial cracks and fissure gradually decreases, and the surface spalling zone becomes more obvious.</p>","PeriodicalId":50331,"journal":{"name":"International Journal of Civil Engineering","volume":"33 14","pages":""},"PeriodicalIF":1.7,"publicationDate":"2024-02-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"139771838","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 0
期刊
International Journal of Civil Engineering
全部 Acc. Chem. Res. ACS Applied Bio Materials ACS Appl. Electron. Mater. ACS Appl. Energy Mater. ACS Appl. Mater. Interfaces ACS Appl. Nano Mater. ACS Appl. Polym. Mater. ACS BIOMATER-SCI ENG ACS Catal. ACS Cent. Sci. ACS Chem. Biol. ACS Chemical Health & Safety ACS Chem. Neurosci. ACS Comb. Sci. ACS Earth Space Chem. ACS Energy Lett. ACS Infect. Dis. ACS Macro Lett. ACS Mater. Lett. ACS Med. Chem. Lett. ACS Nano ACS Omega ACS Photonics ACS Sens. ACS Sustainable Chem. Eng. ACS Synth. Biol. Anal. Chem. BIOCHEMISTRY-US Bioconjugate Chem. BIOMACROMOLECULES Chem. Res. Toxicol. Chem. Rev. Chem. Mater. CRYST GROWTH DES ENERG FUEL Environ. Sci. Technol. Environ. Sci. Technol. Lett. Eur. J. Inorg. Chem. IND ENG CHEM RES Inorg. Chem. J. Agric. Food. Chem. J. Chem. Eng. Data J. Chem. Educ. J. Chem. Inf. Model. J. Chem. Theory Comput. J. Med. Chem. J. Nat. Prod. J PROTEOME RES J. Am. Chem. Soc. LANGMUIR MACROMOLECULES Mol. Pharmaceutics Nano Lett. Org. Lett. ORG PROCESS RES DEV ORGANOMETALLICS J. Org. Chem. J. Phys. Chem. J. Phys. Chem. A J. Phys. Chem. B J. Phys. Chem. C J. Phys. Chem. Lett. Analyst Anal. Methods Biomater. Sci. Catal. Sci. Technol. Chem. Commun. Chem. Soc. Rev. CHEM EDUC RES PRACT CRYSTENGCOMM Dalton Trans. Energy Environ. Sci. ENVIRON SCI-NANO ENVIRON SCI-PROC IMP ENVIRON SCI-WAT RES Faraday Discuss. Food Funct. Green Chem. Inorg. Chem. Front. Integr. Biol. J. Anal. At. Spectrom. J. Mater. Chem. A J. Mater. Chem. B J. Mater. Chem. C Lab Chip Mater. Chem. Front. Mater. Horiz. MEDCHEMCOMM Metallomics Mol. Biosyst. Mol. Syst. Des. Eng. Nanoscale Nanoscale Horiz. Nat. Prod. Rep. New J. Chem. Org. Biomol. Chem. Org. Chem. Front. PHOTOCH PHOTOBIO SCI PCCP Polym. Chem.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1