首页 > 最新文献

2012 International Conference on Lightning Protection (ICLP)最新文献

英文 中文
The electric field of negative upward lightning strikes at the Peissenberg tower, Germany 负向上雷击在德国佩森伯格塔的电场
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344205
M. Manhardt, F. Heidler, K. Stimper
Subject matter of this paper is the analysis of the slow-varying electric fields and the associated currents of the total of 35 negative upward lightning initiated by the Peissenberg tower, Germany. 34 of which were from winter upward lightning and only one from summer upward lightning. It appears that all of the winter upward lightning were initiated without nearby preceding lightning activity (called “self-initiated” lightning) and only the summer lightning was triggered by nearby lightning activity (called “other-triggered” lightning). The slow-varying electric fields of the winter upward lightning showed a fast rise characterized by the 10-to-90% risetime, with an arithmetic mean of 13.8 ms. After attaining the maximum, the electric field turned into a slow decay being characterized by the time on half value which was evaluated to having the arithmetic mean of 441 ms. Transported charges to ground were on average 44.8 C and on maximum 165 C. The maximum value of the electric field was 39.9 kV/m on average, with the highest value being 64.5 kV/m. For the electric fields, higher values were prevented by recovery effects such as the corona from objects at ground and the redistribution of the charge in the thundercloud. Due to these effects, no or only weak correlations were found between the 10-to-90% risetime, the time on half value, the charge, and the maximum of the electric field. From additional measurements with a field mill, it was found that the electric field recovers to the starting level within some seconds.
本文的研究内容是对德国Peissenberg塔引发的35次负向上闪电的慢变电场及其伴随电流进行分析,其中34次为冬季向上闪电,只有1次为夏季向上闪电。似乎所有的冬季上升闪电都是在没有附近闪电活动(称为“自我触发”闪电)的情况下产生的,只有夏季闪电是由附近闪电活动(称为“他人触发”闪电)引发的。冬季上升闪电电场变化缓慢,呈快速上升趋势,上升时间为10 ~ 90%,算术平均值为13.8 ms。在达到最大值后,电场开始缓慢衰减,其特征为半上时间,其算术平均值为441 ms。输送到地面的电荷平均为44.8 C,最大为165 C,电场最大值平均为39.9 kV/m,最大值为64.5 kV/m。对于电场,由于地面物体产生的日冕和雷云中电荷的重新分配等恢复效应,阻止了更高的值。由于这些影响,10% -90%的上升时间、半值时间、电荷和电场最大值之间没有或只有弱相关性。通过现场磨机的额外测量,发现电场在几秒钟内恢复到起始水平。
{"title":"The electric field of negative upward lightning strikes at the Peissenberg tower, Germany","authors":"M. Manhardt, F. Heidler, K. Stimper","doi":"10.1109/ICLP.2012.6344205","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344205","url":null,"abstract":"Subject matter of this paper is the analysis of the slow-varying electric fields and the associated currents of the total of 35 negative upward lightning initiated by the Peissenberg tower, Germany. 34 of which were from winter upward lightning and only one from summer upward lightning. It appears that all of the winter upward lightning were initiated without nearby preceding lightning activity (called “self-initiated” lightning) and only the summer lightning was triggered by nearby lightning activity (called “other-triggered” lightning). The slow-varying electric fields of the winter upward lightning showed a fast rise characterized by the 10-to-90% risetime, with an arithmetic mean of 13.8 ms. After attaining the maximum, the electric field turned into a slow decay being characterized by the time on half value which was evaluated to having the arithmetic mean of 441 ms. Transported charges to ground were on average 44.8 C and on maximum 165 C. The maximum value of the electric field was 39.9 kV/m on average, with the highest value being 64.5 kV/m. For the electric fields, higher values were prevented by recovery effects such as the corona from objects at ground and the redistribution of the charge in the thundercloud. Due to these effects, no or only weak correlations were found between the 10-to-90% risetime, the time on half value, the charge, and the maximum of the electric field. From additional measurements with a field mill, it was found that the electric field recovers to the starting level within some seconds.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"38 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"126956204","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 12
Clarification of the mechanism of wind turbine blade damage taking lightning characteristics into consideration and relevant research project 明确考虑雷电特性的风力机叶片损伤机理及相关研究项目
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344332
S. Yokoyama, Y. Yasuda, M. Minowa, S. Sekioka, K. Yamamoto, N. Honjo, T. Sato
We investigated various types of damages on a wind turbine blades and estimated the possible causes of them. The cause of catastrophic damages such as explosion or falling down is different from that of less serious damages such as a surface tearing. It may be necessary to protect wind turbine blades by means of special measure against severe lightning for example lightning in winter. Also we should clarify the validity of long gap discharge test in the laboratory as the simulation of actual lightning. It leads to establishing appropriate test methods.
我们调查了风力涡轮机叶片上的各种类型的损伤,并估计了它们的可能原因。爆炸或坠落等灾难性损坏的原因与表面撕裂等不太严重的损坏的原因不同。可能有必要采取特殊措施来保护风力涡轮机叶片免受强烈的闪电,例如冬季的闪电。同时,还应明确实验室长间隙放电试验作为实际雷电模拟的有效性。它导致建立适当的测试方法。
{"title":"Clarification of the mechanism of wind turbine blade damage taking lightning characteristics into consideration and relevant research project","authors":"S. Yokoyama, Y. Yasuda, M. Minowa, S. Sekioka, K. Yamamoto, N. Honjo, T. Sato","doi":"10.1109/ICLP.2012.6344332","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344332","url":null,"abstract":"We investigated various types of damages on a wind turbine blades and estimated the possible causes of them. The cause of catastrophic damages such as explosion or falling down is different from that of less serious damages such as a surface tearing. It may be necessary to protect wind turbine blades by means of special measure against severe lightning for example lightning in winter. Also we should clarify the validity of long gap discharge test in the laboratory as the simulation of actual lightning. It leads to establishing appropriate test methods.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"67 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"130643068","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 13
Summary of 2011 direct and nearby lightning strikes to Launch Complex 39B, Kennedy Space Center, Florida 2011年佛罗里达肯尼迪航天中心39B发射场直接和附近雷击的总结
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344321
C. Mata, A. G. Mata
A Lightning Protection System (LPS) was designed and built at Launch Complex 39B (LC39B), at the Kennedy Space Center (KSC), Florida in 2009. This LPS was instrumented with comprehensive meteorological and lightning data acquisition systems that were deployed from late 2010 until mid 2011. The first direct strikes to the LPS were recorded in March of 2011, when a limited number of sensors had been activated. The lightning instrumentation system detected a total of 70 nearby strokes and 19 direct strokes to the LPS, in 2011, 2 of the 19 direct strokes to the LPS had two simultaneous ground attachment points (in both instances one channel terminated on the LPS and the other on the nearby ground). In addition to the 70 nearby strokes, some more distant nearby strokes where captured on video records for which limited data were acquired. Instrumentation deployment chronological milestones, a summary of lightning strikes (direct and nearby), high speed video frames, downconductor currents, and dH/dt and dE/dt typical waveforms for direct and nearby strokes are presented in this paper.
雷电防护系统(LPS)于2009年在佛罗里达州肯尼迪航天中心(KSC)的发射综合体39B (LC39B)设计和建造。从2010年底到2011年中期,该LPS配备了综合气象和闪电数据采集系统。第一次对LPS的直接攻击发生在2011年3月,当时激活的传感器数量有限。雷电仪表系统共检测到70次近雷击和19次对LPS的直接雷击,在2011年,对LPS的19次直接雷击中有2次同时有两个地面附着点(在这两种情况下,一个通道在LPS上终止,另一个在附近的地面上终止)。除了70个附近的笔划外,还有一些较远的附近笔划被记录在视频记录中,这些记录获得了有限的数据。本文介绍了仪器部署时间顺序里程碑、雷击(直接和附近)、高速视频帧、下导体电流以及直接和附近雷击的dH/dt和dE/dt典型波形。
{"title":"Summary of 2011 direct and nearby lightning strikes to Launch Complex 39B, Kennedy Space Center, Florida","authors":"C. Mata, A. G. Mata","doi":"10.1109/ICLP.2012.6344321","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344321","url":null,"abstract":"A Lightning Protection System (LPS) was designed and built at Launch Complex 39B (LC39B), at the Kennedy Space Center (KSC), Florida in 2009. This LPS was instrumented with comprehensive meteorological and lightning data acquisition systems that were deployed from late 2010 until mid 2011. The first direct strikes to the LPS were recorded in March of 2011, when a limited number of sensors had been activated. The lightning instrumentation system detected a total of 70 nearby strokes and 19 direct strokes to the LPS, in 2011, 2 of the 19 direct strokes to the LPS had two simultaneous ground attachment points (in both instances one channel terminated on the LPS and the other on the nearby ground). In addition to the 70 nearby strokes, some more distant nearby strokes where captured on video records for which limited data were acquired. Instrumentation deployment chronological milestones, a summary of lightning strikes (direct and nearby), high speed video frames, downconductor currents, and dH/dt and dE/dt typical waveforms for direct and nearby strokes are presented in this paper.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"32 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"130693893","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 5
Analytical investigation on OPGW strands melting due to DC arc discharge simulating lightning strike 模拟雷击的直流电弧放电导致OPGW股熔化的分析研究
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344238
M. Iwata, T. Ohtaka, Y. Kuzuma, Y. Goda
Some metal strands of OPGW (composite fiber-optic ground wire) are sometimes melted and broken by lightning strikes. DC arc tests simulating lightning strikes have thus been performed to obtain their melting and breaking characteristics. In this paper, calculations regarding these melting characteristics are performed considering the transferred heat and its area from the arc to the strands. The melting characteristics of strands are calculated with an arc current of 0.1 - 100 kA, considering the current prescribed in the IEC standard and the measured actual lightning current. The calculation results of the strand melting duration depending on the arc current show a good agreement with the experimental values obtained in DC arc tests.
OPGW(复合光纤接地线)的一些金属股有时会被雷击熔化和折断。因此,进行了模拟雷击的直流电弧试验,以获得它们的熔化和断裂特性。在本文中,对这些熔化特性进行了计算,考虑了从电弧到钢绞线的传递热量及其面积。考虑到IEC标准规定的电流和实测的实际雷电电流,在0.1 ~ 100ka的电弧电流范围内计算了导线的熔化特性。熔炼时间随电弧电流变化的计算结果与直流电弧试验结果吻合较好。
{"title":"Analytical investigation on OPGW strands melting due to DC arc discharge simulating lightning strike","authors":"M. Iwata, T. Ohtaka, Y. Kuzuma, Y. Goda","doi":"10.1109/ICLP.2012.6344238","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344238","url":null,"abstract":"Some metal strands of OPGW (composite fiber-optic ground wire) are sometimes melted and broken by lightning strikes. DC arc tests simulating lightning strikes have thus been performed to obtain their melting and breaking characteristics. In this paper, calculations regarding these melting characteristics are performed considering the transferred heat and its area from the arc to the strands. The melting characteristics of strands are calculated with an arc current of 0.1 - 100 kA, considering the current prescribed in the IEC standard and the measured actual lightning current. The calculation results of the strand melting duration depending on the arc current show a good agreement with the experimental values obtained in DC arc tests.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"26 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"116562413","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 6
Influence of thunderstorm-like wind velocities on point discharge corona currents 雷暴样风速对点放电电晕电流的影响
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344399
F. Avella, J. Diaz, D. Ariza, O. Escobar, F. Roman
To study the influence of the wind speed on the generation of corona current in two different needles, a wind tunnel was designed and constructed. Needles were tested in a point-to-plane arrangement under laminar air flow. A constant background voltage is applied to the electrode arrangement, while air velocity varied from 0 m/s up to 16 m/s, a wind velocity near to thunderstorm conditions. Results show that the corona onset voltage of the needles is independent of the air velocity; however, the corona current magnitude increases with an increase of the air velocity.
为了研究风速对两针电晕电流产生的影响,设计并建造了风洞。针在层流下的点对平面布置中进行了测试。当风速从0米/秒到16米/秒(接近雷暴条件的风速)变化时,将恒定的背景电压施加到电极布置上。结果表明,针的电晕起始电压与风速无关;日冕电流的大小随风速的增大而增大。
{"title":"Influence of thunderstorm-like wind velocities on point discharge corona currents","authors":"F. Avella, J. Diaz, D. Ariza, O. Escobar, F. Roman","doi":"10.1109/ICLP.2012.6344399","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344399","url":null,"abstract":"To study the influence of the wind speed on the generation of corona current in two different needles, a wind tunnel was designed and constructed. Needles were tested in a point-to-plane arrangement under laminar air flow. A constant background voltage is applied to the electrode arrangement, while air velocity varied from 0 m/s up to 16 m/s, a wind velocity near to thunderstorm conditions. Results show that the corona onset voltage of the needles is independent of the air velocity; however, the corona current magnitude increases with an increase of the air velocity.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"35 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"134052059","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 5
Analysis of lightning detection network data for selected areas in Canada 加拿大选定地区雷电探测网数据分析
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344395
V. Shostak, O. Bormotov, D. Pavanello, W. Janischewskyj, F. Rachidi
An analysis of Canadian Lightning Detection Network (CLDN) data recorded during years 2004 - 2006 is performed for two selected areas in Canada within a 20-km radius around two tall structures: the CN Tower (CNT, 553 m) in Toronto and the Superstack (SS, 380 m) in Sudbury. The explored lightning characteristics include stroke polarity, lake water or land termination (WT or LT), ground stroke densities Ngs, stroke peak currents (including values of I50%, I95%, I5%), distributions of parameters. The results show noticeable differences between characteristics of lightning terminated to lake water and land. In Toronto area (Ngs ≈ 3.24 strokes/(km2·year)), a commonly accepted feature, according to which positive strokes exhibit dominating peak currents in comparison to negative ones, is confirmed only for WT lightning (not close to the CNT), especially in the range of high currents. For LT lightning in the range of current amplitudes close to 50% values, the negative strokes are characterized by larger peaks (by more than 30%) with respect to positive ones. No positive strokes to water were recorded within 5 km near the CNT during the period of analysis. While WT events exhibit a lower Ngs than LT ones, they show larger peak currents. The Sudbury area, characterized by a lower lightning activity (Ngs ≈ 0.91 strokes/(km2·year)), shows the common relation between peak currents of positive and negative polarities (first are dominating). For the SS, the estimated number of upward lightning looks rather low: 0.47 strokes or 0.37 flashes per year. For the CNT, it is about 32 strokes or 14 upward flashes per year. Distributions of Ngs along the distance from the tall objects, beside the increased levels near object, contain dips next to object (up to 3 - 7 km).
对加拿大闪电探测网络(CLDN)在2004 - 2006年间记录的数据进行了分析,这些数据是在加拿大两个选定的区域,在两个高层建筑周围20公里的半径范围内进行的:多伦多的CN塔(CNT, 553米)和萨德伯里的Superstack (SS, 380米)。研究的闪电特征包括闪电极性、湖水或陆地终止(WT或LT)、地面闪电密度、闪电峰值电流(包括I50%、I95%、I5%)、参数分布。结果表明,湖面闪电与陆地闪电的特征存在显著差异。在多伦多地区(ng≈3.24冲程/(km2·年)),一个普遍接受的特征,即与负冲程相比,正冲程在峰值电流中占主导地位,仅在WT闪电(不靠近CNT)中得到证实,特别是在大电流范围内。在电流幅值接近50%的范围内,LT闪电的负冲程比正冲程具有更大的峰值(超过30%)。在分析期间,在CNT附近5公里范围内没有记录到阳性的冲水。虽然小波事件的峰值电流比小波事件低,但它们的峰值电流更大。萨德伯里地区雷电活动较低(Ngs≈0.91次/(km2·年)),显示出正、负极性峰值电流之间的共同关系(首先占主导地位)。对于SS,向上闪电的估计数量看起来相当低:每年0.47次或0.37次闪光。对于CNT来说,每年大约是32次或14次向上闪光。Ngs沿距离高物体的距离分布,除了物体附近水平增加外,在物体旁边有下降(高达3 - 7公里)。
{"title":"Analysis of lightning detection network data for selected areas in Canada","authors":"V. Shostak, O. Bormotov, D. Pavanello, W. Janischewskyj, F. Rachidi","doi":"10.1109/ICLP.2012.6344395","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344395","url":null,"abstract":"An analysis of Canadian Lightning Detection Network (CLDN) data recorded during years 2004 - 2006 is performed for two selected areas in Canada within a 20-km radius around two tall structures: the CN Tower (CNT, 553 m) in Toronto and the Superstack (SS, 380 m) in Sudbury. The explored lightning characteristics include stroke polarity, lake water or land termination (WT or LT), ground stroke densities Ngs, stroke peak currents (including values of I50%, I95%, I5%), distributions of parameters. The results show noticeable differences between characteristics of lightning terminated to lake water and land. In Toronto area (Ngs ≈ 3.24 strokes/(km2·year)), a commonly accepted feature, according to which positive strokes exhibit dominating peak currents in comparison to negative ones, is confirmed only for WT lightning (not close to the CNT), especially in the range of high currents. For LT lightning in the range of current amplitudes close to 50% values, the negative strokes are characterized by larger peaks (by more than 30%) with respect to positive ones. No positive strokes to water were recorded within 5 km near the CNT during the period of analysis. While WT events exhibit a lower Ngs than LT ones, they show larger peak currents. The Sudbury area, characterized by a lower lightning activity (Ngs ≈ 0.91 strokes/(km2·year)), shows the common relation between peak currents of positive and negative polarities (first are dominating). For the SS, the estimated number of upward lightning looks rather low: 0.47 strokes or 0.37 flashes per year. For the CNT, it is about 32 strokes or 14 upward flashes per year. Distributions of Ngs along the distance from the tall objects, beside the increased levels near object, contain dips next to object (up to 3 - 7 km).","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"48 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"134437453","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 7
Site errors estimation and correction for MDF/TOA combined lightning location network MDF/TOA组合闪电定位网的站点误差估计与校正
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344308
Tao Lu, Ming-li Chen, Ya-ping Du
Although, lightning location network (LLN) has been widely used all over the world, its performance is still constrained by “site errors” as long as the direction-finder technique is deployed. Based on lightning data from a regional LLN consisted of 25 MDF/TOA combined sensors, a method for “site errors” estimation and correction was proposed and practiced. By comparing the lightning locations reported by at least 4 sensors between MDF and TOA techniques, the spatial and seasonal signatures of “site errors” for individual sensors were found and discussed. The signatures found are well consistent with those in literature. The “site errors” obtained were then used to correct and improve the accuracy of lightning locations reported by only 2 or 3 sensors. Results showed that the proposed “site errors” correction method could significantly improve the location accuracy of the LLN.
虽然闪电定位网络(LLN)在世界范围内得到了广泛的应用,但只要部署测向器技术,其性能仍然受到“站点误差”的限制。基于由25个MDF/TOA组合传感器组成的区域LLN闪电数据,提出了一种“站点误差”估计和校正方法,并进行了实践。通过比较MDF和TOA技术之间至少4个传感器报告的闪电位置,发现并讨论了单个传感器“站点误差”的空间和季节特征。所发现的签名与文献中的一致。然后利用获得的“位置误差”来修正和提高仅由2或3个传感器报告的闪电位置的准确性。结果表明,提出的“站点误差”校正方法可以显著提高LLN的定位精度。
{"title":"Site errors estimation and correction for MDF/TOA combined lightning location network","authors":"Tao Lu, Ming-li Chen, Ya-ping Du","doi":"10.1109/ICLP.2012.6344308","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344308","url":null,"abstract":"Although, lightning location network (LLN) has been widely used all over the world, its performance is still constrained by “site errors” as long as the direction-finder technique is deployed. Based on lightning data from a regional LLN consisted of 25 MDF/TOA combined sensors, a method for “site errors” estimation and correction was proposed and practiced. By comparing the lightning locations reported by at least 4 sensors between MDF and TOA techniques, the spatial and seasonal signatures of “site errors” for individual sensors were found and discussed. The signatures found are well consistent with those in literature. The “site errors” obtained were then used to correct and improve the accuracy of lightning locations reported by only 2 or 3 sensors. Results showed that the proposed “site errors” correction method could significantly improve the location accuracy of the LLN.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"39 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"122496211","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 2
Grounding resistance of grounding electrode using carbon plate made of woody material 采用木质碳板的接地电极的接地电阻
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344327
H. Shimizu, N. Watanabe
Woodceramics is a carbon material made of woody material and is expected as an eco-material. The woodceramics can be used as an electrical conductor. To estimate the feasibility of the woodceramics as grounding electrode, the woodceramics plate was fabricated and the fundamental properties were investigated as grounding electrode. The resistance and density were measured by simple methods. The resistance of woodceramics plate was sufficiently low when the woodceramics was manufactured under the condition of annealing temperature of higher than 800 °C. The woodceramics plate had about one-ninth density the copper plate. The grounding resistance was also estimated. The grounding resistance of woodceramics electrode per 1 m2 was about 40 Ω and almost equal to that in case that copper grounding electrode was used. Furthermore, the impedance of the woodceramics electrode for surge current was measured. It was confirmed that the magnitude was sufficiently small. It was pointed out that the woodceramics can be applied to the grounding electrode.
木陶瓷是一种由木质材料制成的碳材料,有望成为一种生态材料。木陶瓷可用作导电体。为了评估木陶瓷作为接地电极的可行性,制作了木陶瓷板,并对其基本性能进行了研究。用简单的方法测定了电阻和密度。在高于800℃的退火温度下制备的木陶瓷板材的电阻足够低。木陶瓷板的密度大约是铜板的九分之一。并对接地电阻进行了估计。木陶瓷电极每1 m2的接地电阻约为40 Ω,与使用铜接地电极时的接地电阻基本相等。此外,还测量了木陶瓷电极对浪涌电流的阻抗。经证实,震级足够小。指出了木陶瓷可以应用于接地电极。
{"title":"Grounding resistance of grounding electrode using carbon plate made of woody material","authors":"H. Shimizu, N. Watanabe","doi":"10.1109/ICLP.2012.6344327","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344327","url":null,"abstract":"Woodceramics is a carbon material made of woody material and is expected as an eco-material. The woodceramics can be used as an electrical conductor. To estimate the feasibility of the woodceramics as grounding electrode, the woodceramics plate was fabricated and the fundamental properties were investigated as grounding electrode. The resistance and density were measured by simple methods. The resistance of woodceramics plate was sufficiently low when the woodceramics was manufactured under the condition of annealing temperature of higher than 800 °C. The woodceramics plate had about one-ninth density the copper plate. The grounding resistance was also estimated. The grounding resistance of woodceramics electrode per 1 m2 was about 40 Ω and almost equal to that in case that copper grounding electrode was used. Furthermore, the impedance of the woodceramics electrode for surge current was measured. It was confirmed that the magnitude was sufficiently small. It was pointed out that the woodceramics can be applied to the grounding electrode.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"52 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"122646810","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 2
Lightning induced voltages in simple configurations of underground cables 地下电缆简单配置中的雷击感应电压
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344394
L. Diaz, M. Martínez, J. Ramirez, M. Rubinstein
In this paper, the effect of the geometrical configuration of underground conductors and of the relative location of the lightning strike on induced voltages from lightning is studied. The position of the strike point that leads to the highest induced voltage is determined for buried cables for each configuration. The results show that the maximum voltages tend to appear at the extremities of the cables and at the point closest to the strike point. The overvoltages are lower for bare cables when compared to insulated cables. Overvoltage levels for typical negative subsequent return stroke currents used in this paper represent a risk for low voltage underground feeders and electronic, communication and control circuits.
本文研究了地下导线的几何形态和雷击的相对位置对雷击感应电压的影响。对于不同配置的地埋电缆,应确定感应电压最高的触电点位置。结果表明,最大电压往往出现在电缆的两端和最接近触击点的地方。与绝缘电缆相比,裸电缆的过电压较低。本文中使用的典型负后续回程行程电流的过电压水平代表了低压地下馈线和电子,通信和控制电路的风险。
{"title":"Lightning induced voltages in simple configurations of underground cables","authors":"L. Diaz, M. Martínez, J. Ramirez, M. Rubinstein","doi":"10.1109/ICLP.2012.6344394","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344394","url":null,"abstract":"In this paper, the effect of the geometrical configuration of underground conductors and of the relative location of the lightning strike on induced voltages from lightning is studied. The position of the strike point that leads to the highest induced voltage is determined for buried cables for each configuration. The results show that the maximum voltages tend to appear at the extremities of the cables and at the point closest to the strike point. The overvoltages are lower for bare cables when compared to insulated cables. Overvoltage levels for typical negative subsequent return stroke currents used in this paper represent a risk for low voltage underground feeders and electronic, communication and control circuits.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"11 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"121234157","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 3
Investigation of compacted and extended objects lightning protection effectiveness on models using artificial clouds of charged water aerosol 使用带电水气溶胶人工云的模式对压缩和扩展物体防雷效果的研究
Pub Date : 2012-11-12 DOI: 10.1109/ICLP.2012.6344280
A. Temnikov, L. Chernensky, A. Orlov, M. Sokolova, T. Gerastenok, O. Belova
Results of the experimental investigations and physical simulation of the processes of lightning affection of the compacted and extended objects on models and the investigation of its lightning protection effectiveness using artificial charged aerosol clouds are presented. Peculiarities of affection of the grounded objects by the discharges from artificial charged aerosol clouds are presented and analyzed. Influence of the characteristics of lightning rod and object models (or lightning conductor and phase wire models) on the process of their affection by the discharge from charged aerosol has been analyzed. Comparison of the experimental results with the calculated and experimental methods of determination of the compacted and extended object lightning protection (in context of power objects) has been fulfilled. Recommendations on the improvement of lightning protection of the existing and projecting power energy objects have been proposed.
本文介绍了雷电过程的实验研究和物理模拟结果,以及压缩和扩展物体对模型的影响,以及利用人工带电气溶胶云对其防雷效果的研究。介绍并分析了人工带电气溶胶云的放电对地物影响的特点。分析了避雷针和物体模型(或避雷针和相线模型)的特性对其受带电气溶胶放电影响过程的影响。将实验结果与计算和实验确定的压缩和扩展对象防雷(电源对象)的方法进行了比较。提出了改进现有和投射电力能量物体防雷的建议。
{"title":"Investigation of compacted and extended objects lightning protection effectiveness on models using artificial clouds of charged water aerosol","authors":"A. Temnikov, L. Chernensky, A. Orlov, M. Sokolova, T. Gerastenok, O. Belova","doi":"10.1109/ICLP.2012.6344280","DOIUrl":"https://doi.org/10.1109/ICLP.2012.6344280","url":null,"abstract":"Results of the experimental investigations and physical simulation of the processes of lightning affection of the compacted and extended objects on models and the investigation of its lightning protection effectiveness using artificial charged aerosol clouds are presented. Peculiarities of affection of the grounded objects by the discharges from artificial charged aerosol clouds are presented and analyzed. Influence of the characteristics of lightning rod and object models (or lightning conductor and phase wire models) on the process of their affection by the discharge from charged aerosol has been analyzed. Comparison of the experimental results with the calculated and experimental methods of determination of the compacted and extended object lightning protection (in context of power objects) has been fulfilled. Recommendations on the improvement of lightning protection of the existing and projecting power energy objects have been proposed.","PeriodicalId":400743,"journal":{"name":"2012 International Conference on Lightning Protection (ICLP)","volume":"21 1","pages":"0"},"PeriodicalIF":0.0,"publicationDate":"2012-11-12","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":null,"resultStr":null,"platform":"Semanticscholar","paperid":"129100153","PeriodicalName":null,"FirstCategoryId":null,"ListUrlMain":null,"RegionNum":0,"RegionCategory":"","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":"","EPubDate":null,"PubModel":null,"JCR":null,"JCRName":null,"Score":null,"Total":0}
引用次数: 3
期刊
2012 International Conference on Lightning Protection (ICLP)
全部 Acc. Chem. Res. ACS Applied Bio Materials ACS Appl. Electron. Mater. ACS Appl. Energy Mater. ACS Appl. Mater. Interfaces ACS Appl. Nano Mater. ACS Appl. Polym. Mater. ACS BIOMATER-SCI ENG ACS Catal. ACS Cent. Sci. ACS Chem. Biol. ACS Chemical Health & Safety ACS Chem. Neurosci. ACS Comb. Sci. ACS Earth Space Chem. ACS Energy Lett. ACS Infect. Dis. ACS Macro Lett. ACS Mater. Lett. ACS Med. Chem. Lett. ACS Nano ACS Omega ACS Photonics ACS Sens. ACS Sustainable Chem. Eng. ACS Synth. Biol. Anal. Chem. BIOCHEMISTRY-US Bioconjugate Chem. BIOMACROMOLECULES Chem. Res. Toxicol. Chem. Rev. Chem. Mater. CRYST GROWTH DES ENERG FUEL Environ. Sci. Technol. Environ. Sci. Technol. Lett. Eur. J. Inorg. Chem. IND ENG CHEM RES Inorg. Chem. J. Agric. Food. Chem. J. Chem. Eng. Data J. Chem. Educ. J. Chem. Inf. Model. J. Chem. Theory Comput. J. Med. Chem. J. Nat. Prod. J PROTEOME RES J. Am. Chem. Soc. LANGMUIR MACROMOLECULES Mol. Pharmaceutics Nano Lett. Org. Lett. ORG PROCESS RES DEV ORGANOMETALLICS J. Org. Chem. J. Phys. Chem. J. Phys. Chem. A J. Phys. Chem. B J. Phys. Chem. C J. Phys. Chem. Lett. Analyst Anal. Methods Biomater. Sci. Catal. Sci. Technol. Chem. Commun. Chem. Soc. Rev. CHEM EDUC RES PRACT CRYSTENGCOMM Dalton Trans. Energy Environ. Sci. ENVIRON SCI-NANO ENVIRON SCI-PROC IMP ENVIRON SCI-WAT RES Faraday Discuss. Food Funct. Green Chem. Inorg. Chem. Front. Integr. Biol. J. Anal. At. Spectrom. J. Mater. Chem. A J. Mater. Chem. B J. Mater. Chem. C Lab Chip Mater. Chem. Front. Mater. Horiz. MEDCHEMCOMM Metallomics Mol. Biosyst. Mol. Syst. Des. Eng. Nanoscale Nanoscale Horiz. Nat. Prod. Rep. New J. Chem. Org. Biomol. Chem. Org. Chem. Front. PHOTOCH PHOTOBIO SCI PCCP Polym. Chem.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
0
微信
客服QQ
Book学术公众号 扫码关注我们
反馈
×
意见反馈
请填写您的意见或建议
请填写您的手机或邮箱
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
现在去查看 取消
×
提示
确定
Book学术官方微信
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术
文献互助 智能选刊 最新文献 互助须知 联系我们:info@booksci.cn
Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。
Copyright © 2023 Book学术 All rights reserved.
ghs 京公网安备 11010802042870号 京ICP备2023020795号-1